Energy benefit of a cascade liquid desiccant dehumidification in a desiccant and evaporative cooling-assisted building air-conditioning system

Authors
Park, Joon-YoungDong, Hye-WonCho, Hye-JinJeong, Jae-Weon
Issue Date
Jan-2019
Publisher
PERGAMON-ELSEVIER SCIENCE LTD
Keywords
Liquid desiccant system; Evaporative cooling system; 100% outdoor air system
Citation
Applied Thermal Engineering, v.147, pp.291 - 301
Indexed
SCIE
SCOPUS
Journal Title
Applied Thermal Engineering
Volume
147
Start Page
291
End Page
301
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/148556
DOI
10.1016/j.applthermaleng.2018.10.101
ISSN
1359-4311
Abstract
The main objective of this study was to estimate the impact of dehumidification with a cascade liquid desiccant on the primary energy consumption in a liquid desiccant and evaporative cooling-assisted 100% outdoor air system. Detailed energy simulations were performed for two systems serving an identical office space: the conventional liquid desiccant and indirect/direct evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS) (i.e., Case 1) having a single-stage liquid desiccant dehumidification section, and a retrofit case of the LD-IDECOAS having a cascade liquid desiccant section (i.e., Case 2) consisting of a two-stage liquid desiccant dehumidifier. The results showed that Case 2 consumed 12% less primary energy under the peak load condition and 17.4% less primary energy during the cooling season. The overall thermal and primary coefficients of performance of Case 2 were 0.78 and 2.05, respectively, whereas those of Case 1 were 0.65 and 1.45, respectively. In addition, it was also observed that Case 2 could provide lower supply air temperature to the conditioned space compared with Case 1 owing to enhanced evaporative cooling performance, which was mainly caused by enhanced dehumidification in the cascade liquid desiccant section. The lower supply air temperature resulted in reductions in fan and pump energy consumptions during the operation.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE