Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

축열재 일체형 열전소자 적용 천장 복사 냉방 패널의 에너지 성능 분석Analysis Energy Performance of Ceiling Radiant Cooling Panel Using Thermoelectric Modules with Integrated Heat Storage Material

Other Titles
Analysis Energy Performance of Ceiling Radiant Cooling Panel Using Thermoelectric Modules with Integrated Heat Storage Material
Authors
강용권천성용정재원
Issue Date
Nov-2018
Publisher
대한설비공학회
Keywords
phase change material; thermoelectric modules; radiant cooling; 상변화물질; 열전소자; 복사냉방
Citation
대한설비공학회 2018년도 동계학술발표대회 논문집, pp.132 - 135
Indexed
OTHER
Journal Title
대한설비공학회 2018년도 동계학술발표대회 논문집
Start Page
132
End Page
135
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/148955
Abstract
This study proposes a phase change material based radiant cooling panel with thermoelectric modules (PCM-TERCP) and evaluate its performance characteristics during melting process of phase change materials in designed condition. The PCM-TERCP consists of phase change materials (PCMs), thermoelectric modules (TEMs) and aluminium panels. TEMs operate to freeze the PCM, and PCM stores the cooling thermal energy to maintain the constant surface temperature of the panel for radiant cooling. The main purpose of thermal energy storage systems is shifting the cooling season’s electricity consumption from day-time to night-time. Therefore, PCM-TECRP can implement the off-peak operation and it is expected that energy can be saved. Therefore, we constructed the mock up model of PCM-TERCP to identify the factors that affect the discharging process of PCM-TERCP. The mock up model of PCM-TERCP was made of top aluminium panel with three TEMs attached on the upper surface of the top panel, and a heat sink was attached on the hot side of each TEM to remove the heat, and two PCM pouches were installed between top and bottom panel. In addition, the melting temperature of PCM and target surface temperature of bottom panel were designed to be 16℃. Also, the room temperature was set to be 24℃. As a result, radiative cooling was operating a temperature range of 16-20℃ for 3 hours.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE