G-parameter를 이용한 직류 마이크로그리드의 컨버터 상호 안정도 분석 및 가상 임피던스를 이용한 안정도 향상Stability Analysis Using G-Parameters of Converters Constituting DC Microgrid and Stability Enhancement Through Virtual Impedance
- Other Titles
- Stability Analysis Using G-Parameters of Converters Constituting DC Microgrid and Stability Enhancement Through Virtual Impedance
- Authors
- 이재석; 이기영; 김래영
- Issue Date
- Oct-2018
- Publisher
- 전력전자학회
- Keywords
- DC microgrid; Stability analysis; G-parameter; Virtual impedance
- Citation
- 전력전자학회 논문지, v.23, no.5, pp.321 - 327
- Indexed
- KCI
- Journal Title
- 전력전자학회 논문지
- Volume
- 23
- Number
- 5
- Start Page
- 321
- End Page
- 327
- URI
- https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/149201
- DOI
- 10.6113/TKPE.2018.23.5.321
- ISSN
- 1229-2214
- Abstract
- DC microgrid system composed of multiple converters has a tendency to make the system unstable due to the interaction of converters. To solve this problem, in this paper, the interaction between cascaded converters with LC input filter is analyzed with impedance modeling using g-parameter. The input impedance and the output impedance of the system can be obtained through this technique. The stability of the system can be determined by applying Middlebrook’s stability criterion to the impedance. Virtual impedance is added to the controller to enhance stability. The validity of the analysis is verified by the result of several simulations and experiments.
- Files in This Item
-
Go to Link
- Appears in
Collections - 서울 공과대학 > 서울 전기공학전공 > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.