Comparison of Dehumidification Performance of A Single and Two Stage Dehumidifiers In a Liquid Desiccant-Assisted Dedicated Outdoor Air Systemopen access

Authors
Park, Joon-YoungJeong, Jae Weon
Issue Date
Jun-2018
Publisher
SIY indoor Air Information
Keywords
Liquid desiccant system; Cascade liquid desiccant; Dedicated outdoor air system
Citation
Proceedings of Roomvent and Ventilation 2018 Track 3, pp.535 - 540
Indexed
OTHER
Journal Title
Proceedings of Roomvent and Ventilation 2018 Track 3
Start Page
535
End Page
540
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/149789
Abstract
The aim of this study is to investigate the dehumidification performance and energy conservation of a two-stage liquid desiccant dehumidifier and a single-stage dehumidifier. To enhance the dehumidification performance, a cascade liquid desiccant (CLD) system was applied in an outdoor air unit to adjust the target humidity condition of the induced outdoor air. The CLD consists of a two-stage liquid desiccant dehumidifier unit to carry out deep dehumidification of process air. Process air is dehumidified twice by the CLD system to improve the dehumidification performance of process air compared to a single dehumidifier. The single and cascade liquid desiccant systems were integrated with water-side free cooling using cooling towers for desiccant solution cooling. The energy consumption performance of both systems was evaluated through simulation when operating in an office space as a dedicated outdoor air system (DOAS). The thermal load of a model office space was estimated using TRNSYS 17, and the cooling coil load of DOAS was predicted using a commercial equation solver program. The results show that compared to a single dehumidifier system, CLD requires a lower cooling coil load.
Files in This Item
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE