Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

충전탑식 대향류형 액체식 제습 시스템의 제습 수용액 온도 변화에 따른 제습 성능 분석Dehumidification performance of a packed bed counter-flow type liquid desiccant system with the change of a desiccant solution temperature

Other Titles
Dehumidification performance of a packed bed counter-flow type liquid desiccant system with the change of a desiccant solution temperature
Authors
조혜진천성용최은지정재원
Issue Date
Nov-2017
Publisher
한국건축친환경설비학회
Keywords
액체식 제습 시스템; 대향류형; 제습 성능; 실험 연구; 염화 리튬 수용액; Liquid desiccant system; counter-flow type; dehumidification performance; experiments; lithium chloride aqueous solution
Citation
한국건축친환경설비학회 추계학술발표대회 논문집, pp.203 - 204
Indexed
OTHER
Journal Title
한국건축친환경설비학회 추계학술발표대회 논문집
Start Page
203
End Page
204
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/151147
Abstract
The purpose of this paper is to analyze the dehumidification performance of a packed bed counter-flow type liquid desiccant (LD) system with the change of desiccant solution temperature when operating this type of absorber unit. In this study, lithium chloride (LiCl) aqueous solution was used as a desiccant solution for its higher dehumidification efficiency and lower vapor pressure. The dehumidification experiments were conducted as an inlet desiccant solution temperature varied from 15℃ to 30℃, and inlet air conditions are set through a test chamber based on the average outdoor air conditions in summer. The moisture removal rate and dehumidification efficiency were calculated to analyze the effect of inlet desiccant solution temperature on the performance of the proposed liquid desiccant system. The results show that the dehumidification performance of this type of absorber is highest when the solution inlet temperature is 15℃, and sharply decreases when the solution temperature reaches 30℃. To find the optimal solution inlet temperature, however, further studies considering energy consumptions are required because cooling the solution to a lower temperature results in higher energy consumption.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE