Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Energy-Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanroomsopen access

Authors
Jo, Min-SukShin, Jang-HoonKim, Won-JunJeong, Jae-Weon
Issue Date
Nov-2017
Publisher
MDPI AG
Keywords
semiconductor cleanroom; make-up air unit; pressurized water atomizer; adiabatic humidification; energy conservation
Citation
Energies, v.10, no.11, pp.1 - 23
Indexed
SCIE
SCOPUS
Journal Title
Energies
Volume
10
Number
11
Start Page
1
End Page
23
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/151273
DOI
10.3390/en10111774
ISSN
1996-1073
Abstract
This paper aimed to evaluate the applicability of adiabatic humidification in the heating, ventilation, and air conditioning (HVAC) systems of semiconductor cleanrooms. Accurate temperature and humidity control are essential in semiconductor cleanrooms and high energy consumption steam humidification is commonly used. Therefore, we propose an adiabatic humidification system employing a pressurized water atomizer to reduce the energy consumption. The annual energy consumption of three different HVAC systems were analyzed to evaluate the applicability of adiabatic humidification. The studied cases were as follows: (1) CASE 1: a make-up air unit (MAU) with a steam humidifier, a dry cooling coil (DCC), and a fan filter unit (FFU); (2) CASE 2: a MAU with the pressurized water atomizer, a DCC, and a FFU; and (3) CASE 3: a MAU, a DCC, and a FFU, and the pressurized water atomizer installed in the return duct. The energy saving potential of adiabatic humidification over steam humidification has been proved, with savings of 8% and 23% in CASE 2 and CASE 3 compared to CASE 1, respectively. Furthermore, the pressurized water atomizer installed in the return duct exhibits greater energy saving effect than when installed in the MAU.
Files in This Item
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE