Experimental verification of a virtual water flowmeter applicable to air conditioning systems

Authors
Kim, Min-HwiJeong, Jae-Weon
Issue Date
Nov-2017
Publisher
ELSEVIER SCIENCE SA
Keywords
Virtual flowmeter; Pump flow rate measurement; Initial test procedure; Experimental verification
Citation
Energy and Buildings, v.155, pp.425 - 438
Indexed
SCIE
SCOPUS
Journal Title
Energy and Buildings
Volume
155
Start Page
425
End Page
438
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/151368
DOI
10.1016/j.enbuild.2017.09.050
ISSN
0378-7788
Abstract
The main purpose of this research is to suggest a virtual water flowmeter applicable in hydraulic systems with low-cost sensors. Practical procedures for realizing virtual water flowmeters for constant flow pumps (i.e., Cases 1 and 2) and variable flow pumps (i.e., Cases 3 and 4) are proposed in this paper. In Case 1, for measuring the water flow rate through a constant flow pump, the pump head was measured and the water flow rate was estimated using the pump characteristic curve obtained from the manufacturer or by deriving an empirical model based on the field measurement data. In Case 2, the water flow rate through a valve with a constant flow pump was estimated by measuring the pressure head between the valve and the valve opening position. The valve characteristic curve can be obtained by deriving an empirical model based on the initial field test results. The water flow rate through the variable flow pump was calculated, using the pump affinity laws and an empirical model, by measuring the frequency (i.e., Case 3) or input power (i.e., Case 4). The initial setup and test procedures for virtual flowmeters are also proposed in this research for practical use in the field. To verify the proposed procedures, experiments were conducted using constant and variable flow pumps in a pilot system. It was found that the virtual water flowmeters showed 2.9% to 6.7% of root mean square error from Case 1 to Case 4, compared with an ultrasonic water flowmeter, through long-term experimental verification.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE