Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Energy performance prediction of thermoelectric ceiling radiant panels with a dedicated outdoor air system

Authors
Lim, HansolShin, JanghoonLi, ShiyingCho, Hye-JinJeong, Jae Weon
Issue Date
Sep-2017
Publisher
AIVC
Keywords
Dedicated outdoor air system; radiant cooling; cooled ceiling; thermoelectric modules
Citation
Proceedings of 2017 AIVC Conference, pp.613 - 621
Indexed
OTHER
Journal Title
Proceedings of 2017 AIVC Conference
Start Page
613
End Page
621
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/151581
Abstract
This paper proposes a dedicated outdoor air system (DOAS) with thermoelectric module radiant cooling panels (TEM-RCP). The DOAS involves the concept of a decoupled system with a parallel sensible cooling unit. This concept implies decoupling of ventilation and airconditioning functions. The DOAS treats latent loads from outside air intake as a 100 % OA ventilation system. Additionally, a parallel sensible cooling unit, such as ceiling radiant cooling panel (CRCP), generally removes sensible loads. In the study, the variable air volume system and DOAS CRCP using chilled water were also considered as a conventional HVAC system and traditional parallel cooling unit of DOAS, respectively. The two cases were compared to investigate the possibility of applying TEM-RCP on DOAS. Mathematical simulation models were developed, and the operating and annual energy consumptions for all three cases were estimated. The results indicated that the thermal performance was satisfied in all cases including the proposed systems. The proposed system resulted in annual energy consumption savings of 44.5 % when compared with the variable air volume system. On the other hands, the energy consumption of TEM-RCP exceeded that of the CRCP by 33 % due to its low coefficient of performance (COP) and additional energy from heat rejection. The proposed system did not exhibit benefits in terms of energy consumption when compared with that of the DOAS CRCP. However, it could be easily controlled by using input current without refrigerants and still continue to display energy saving potential when compared with the VAV system.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE