Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

제습증발냉각기반 전외기 공조시스템의 지중공간 적용에 따른 1차 에너지 소비분석

Authors
최은지최병남정재원
Issue Date
Jun-2017
Publisher
대한설비공학회
Citation
한국건축친환경설비학회논문집, pp.553 - 556
Indexed
OTHER
Journal Title
한국건축친환경설비학회논문집
Start Page
553
End Page
556
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/152090
Abstract
The purpose of this paper is to evaluate the applicability of a liquid desiccant and evaporative cooling assisted 100% out door air system (LD-IDECOAS) in underground spaces. Detailed energy simulation is performed for estimating the energy saving potential of the LD-IDECOAS. Simulation is conducted using TRNSYS 17 and a commercial engineering equation solver program (EES). The district heating system in the LD-IDECOAS supplies heat energy for regeneration of desiccant. Thermal load of the underground spaces shows different pattern compared with that of the above ground space. Thermal load of underground space showed smaller variation compared with that of above ground space because of less changes of surroundings. As a results, LD-IDECOAS of underground spaces is show energy saving potential compared to the LD-IDECOAS of above ground space.