수중건물에 적용된 외기전담시스템의 연간에너지 소비분석Annual Energy Consumption Analysis of Dedicated Outdoor Air System in an Underwater Building
- Other Titles
- Annual Energy Consumption Analysis of Dedicated Outdoor Air System in an Underwater Building
- Authors
- 조민석; 김희정; 정재원
- Issue Date
- Oct-2016
- Publisher
- 대한건축학회
- Keywords
- 수중건물; 외기전담 시스템; 에너지 소비량; underwater building; dedicated outdoor air system; energy consumption; seawater free-cooling
- Citation
- 2016 대한건축학회 추계학술발표대회논문집, v.36, no.2, pp.659 - 660
- Indexed
- OTHER
- Journal Title
- 2016 대한건축학회 추계학술발표대회논문집
- Volume
- 36
- Number
- 2
- Start Page
- 659
- End Page
- 660
- URI
- https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/153675
- ISSN
- 2287-5786
- Abstract
- The purpose of this study was to compare the annual energy consumptions of dedicated outdoor air system (DOAS) in the above ground and the underwater buildings. The normal building above the ground is located in Ulsan, South Korea whereas the underwater building is located at 20m below mean sea level in Ulsan. The sensible and latent loads of the each model building are calculated by using TRNSYS 17 program. In the case of an underwater building, because materials of building and component of DOAS are different from the normal building, the result showed that the thermal load of the underwater office building showed relatively low and constant annual heating and cooling loads compared with that of normal building. Based on thermal loads, the performance of DOAS is calculated through a commercial engineering equation solver (EES). As a result, the DOAS applied in the underwater building showed 52% energy conservation effect than DOAS applied in the normal building.
- Files in This Item
-
Go to Link
- Appears in
Collections - 서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.