Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

A Simplified model for estimating the regeneration effectiveness of a counter flow regenerator for a liquid desiccant system

Full metadata record
DC Field Value Language
dc.contributor.authorKim, M.H.-
dc.contributor.authorJo, H.J.-
dc.contributor.authorJeong, Jae Weon-
dc.date.accessioned2022-07-16T01:49:44Z-
dc.date.available2022-07-16T01:49:44Z-
dc.date.created2021-05-13-
dc.date.issued2014-11-
dc.identifier.urihttps://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/158544-
dc.description.abstractThe performance of a regenerator using lithium chloride (LiCl) as a desiccant solution was investigated, and experimental research was conducted to observe the performance of the regenerator. The experimental data pool for the regenerator was generated by collecting data from the literature. A response surface method was also used to investigate single parameters and their interactions that have significant effects on the regenerative performance of the regenerator of a liquid desiccant system. Based on this analysis, a first-order linear regression equation was derived as a function of major parameters and interactions, to predict the regeneration effectiveness. The experimental data from the pilot unit were obtained under various operational conditions. Finally, the results of the model and the experimental data were compared. The predicted effectiveness values returned from the derived model show good agreement with the experimental data.-
dc.language영어-
dc.language.isoen-
dc.publisherInternational Building Performance Simulation Association (IBPSA)-
dc.titleA Simplified model for estimating the regeneration effectiveness of a counter flow regenerator for a liquid desiccant system-
dc.typeArticle-
dc.contributor.affiliatedAuthorJeong, Jae Weon-
dc.identifier.bibliographicCitationASim2014 Conference Proceedings, pp.846 - 853-
dc.relation.isPartOfASim2014 Conference Proceedings-
dc.citation.titleASim2014 Conference Proceedings-
dc.citation.startPage846-
dc.citation.endPage853-
dc.type.rimsART-
dc.type.docTypeProceeding-
dc.description.journalClass3-
dc.description.isOpenAccessN-
dc.description.journalRegisteredClassother-
dc.subject.keywordAuthorLiquid desiccant system-
dc.subject.keywordAuthorregenerator-
dc.subject.keywordAuthorregeneration effectiveness-
dc.identifier.urlhttp://ibpsa.org/proceedings/asim2014/190_AsimD5-29-279.pdf-
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE