An active feedforward compensation for a current harmonics reduction in three-phase grid-connected inverters

Authors
Park, Byong-JunChoi, Ki-YoungKim, Rae-Young
Issue Date
Jan-2014
Publisher
IEEE
Keywords
Active feedforward; harmonic compensation; low frequency transformer; low order harmonic; THD; weak grid
Citation
IECON Proceedings (Industrial Electronics Conference), pp.400 - 405
Indexed
SCOPUS
Journal Title
IECON Proceedings (Industrial Electronics Conference)
Start Page
400
End Page
405
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/160873
DOI
10.1109/IECON.2013.6699169
ISSN
1553-572X
Abstract
The paper discusses the influence of a grid impedance, especially for a leakage inductance of a grid side transformer. The grid impedance does not usually take into account during the design stage of the current controller. As a result, low order harmonics in the grid current are distorted. In this paper, the active feed-forward compensation method is proposed for the purpose of attenuating the current distortion. The proposed method can be applied to L filter as well as LCL filter. The effectiveness of the method is verified through various simulations and experiments based on a 1.5kW voltage source inverter prototype.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 전기공학전공 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Kim, Rae Young photo

Kim, Rae Young
COLLEGE OF ENGINEERING (MAJOR IN ELECTRICAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE