Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

상암 DMC 지역냉방 냉열사용량 분석에 의한 실제 부하율 예측Prediction of Actual Load Factors Based on the User Data Analysis of District Cooling in Sangam DMC

Other Titles
Prediction of Actual Load Factors Based on the User Data Analysis of District Cooling in Sangam DMC
Authors
류동원정주현고명준허진혁문승재이재헌유호선이창준김진배
Issue Date
Jul-2011
Publisher
대한설비공학회
Keywords
Diversity factor(동시부하율); Load factor(부하율); District cooling(지역냉방)
Citation
대한설비공학회 2011년도 하계학술발표대회 논문집, no. , pp.539 - 544
Indexed
OTHER
Journal Title
대한설비공학회 2011년도 하계학술발표대회 논문집
Start Page
539
End Page
544
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/167965
Abstract
In order to estimate the capacity increase of cooling plant for the case of saturated occupancy in Sangam DMC, various load factors including diversity factor are analyzed based on the user data during summer season in 2010. The loss rate between supply and demand sides is also evaluated. The most meaningful results include that the predicted diversity factor and loss rate are found to be 0.67 and 0.03, respectively. Further studies, e.g. multi-year data analysis and alternative cooling load-occupancy rate relation, are needed for determining more reasonable load factors.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 기계공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Moon, Seung Jae photo

Moon, Seung Jae
COLLEGE OF ENGINEERING (SCHOOL OF MECHANICAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE