Enhancement and Homogenization of Indoor Air Quality in a Classroom Using a Vertical Airflow Ventilation Scheme
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Park, Su-Hoon | - |
dc.contributor.author | Lee, Kyung-Rae | - |
dc.contributor.author | Yook, Se-Jin | - |
dc.contributor.author | Koo, Hyun Bon | - |
dc.date.accessioned | 2022-10-25T07:40:58Z | - |
dc.date.available | 2022-10-25T07:40:58Z | - |
dc.date.created | 2022-10-06 | - |
dc.date.issued | 2022-09 | - |
dc.identifier.issn | 2305-6304 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/172565 | - |
dc.description.abstract | Since air quality has a great influence on students' health and learning ability, enhancing air quality in classrooms is important. Currently, widely distributed ventilation systems operate by moving airflow horizontally from ventilation inlets and outlets on the ceiling. This method can reduce the average pollution in a space by diluting it through air exchange; however, it is limited regarding homogeneous cleanliness due to air stagnation at some locations. Therefore, in this study, a new ventilation system was devised to improve indoor air quality and spatial homogeneity by installing ventilation inlets on the ceiling and numerous outlets on the floor, creating a vertical airflow in the interior space; this system was then applied to a middle school classroom. Using the age of air as an index, air quality improvement between the existing and newly designed ventilation systems was compared. In the classroom with the existing ventilation system, the age of air was low in the area near the ventilation inlets, while air congestion areas were widely distributed and air age was high near the outlets. Conversely, in the vertical airflow classroom, the average age of air was approximately 15% lower than that with the existing ventilation system, and the deviation of air age for each position in the classroom space was also reduced, showing a uniform air age distribution. Therefore, the vertical airflow ventilation system proposed in this study can be an effective ventilation scheme for enhancing and homogenizing indoor air quality. | - |
dc.language | 영어 | - |
dc.language.iso | en | - |
dc.publisher | MDPI | - |
dc.title | Enhancement and Homogenization of Indoor Air Quality in a Classroom Using a Vertical Airflow Ventilation Scheme | - |
dc.type | Article | - |
dc.contributor.affiliatedAuthor | Yook, Se-Jin | - |
dc.identifier.doi | 10.3390/toxics10090545 | - |
dc.identifier.scopusid | 2-s2.0-85138629639 | - |
dc.identifier.wosid | 000856740400001 | - |
dc.identifier.bibliographicCitation | TOXICS, v.10, no.9, pp.1 - 14 | - |
dc.relation.isPartOf | TOXICS | - |
dc.citation.title | TOXICS | - |
dc.citation.volume | 10 | - |
dc.citation.number | 9 | - |
dc.citation.startPage | 1 | - |
dc.citation.endPage | 14 | - |
dc.type.rims | ART | - |
dc.type.docType | Article | - |
dc.description.journalClass | 1 | - |
dc.description.isOpenAccess | Y | - |
dc.description.journalRegisteredClass | scie | - |
dc.description.journalRegisteredClass | scopus | - |
dc.relation.journalResearchArea | Environmental Sciences & Ecology | - |
dc.relation.journalResearchArea | Toxicology | - |
dc.relation.journalWebOfScienceCategory | Environmental Sciences | - |
dc.relation.journalWebOfScienceCategory | Toxicology | - |
dc.subject.keywordPlus | PERFORMANCE | - |
dc.subject.keywordPlus | CFD | - |
dc.subject.keywordPlus | LOCATION | - |
dc.subject.keywordPlus | WARD | - |
dc.subject.keywordPlus | AGE | - |
dc.subject.keywordAuthor | classroom | - |
dc.subject.keywordAuthor | ventilation | - |
dc.subject.keywordAuthor | indoor air quality | - |
dc.subject.keywordAuthor | age of air | - |
dc.subject.keywordAuthor | computational fluid dynamics | - |
dc.identifier.url | https://www.mdpi.com/2305-6304/10/9/545 | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1365
COPYRIGHT © 2021 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.