Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Enhancement and Homogenization of Indoor Air Quality in a Classroom Using a Vertical Airflow Ventilation Schemeopen access

Authors
Park, Su-HoonLee, Kyung-RaeYook, Se-JinKoo, Hyun Bon
Issue Date
Sep-2022
Publisher
MDPI
Keywords
classroom; ventilation; indoor air quality; age of air; computational fluid dynamics
Citation
TOXICS, v.10, no.9, pp.1 - 14
Indexed
SCIE
SCOPUS
Journal Title
TOXICS
Volume
10
Number
9
Start Page
1
End Page
14
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/172565
DOI
10.3390/toxics10090545
ISSN
2305-6304
Abstract
Since air quality has a great influence on students' health and learning ability, enhancing air quality in classrooms is important. Currently, widely distributed ventilation systems operate by moving airflow horizontally from ventilation inlets and outlets on the ceiling. This method can reduce the average pollution in a space by diluting it through air exchange; however, it is limited regarding homogeneous cleanliness due to air stagnation at some locations. Therefore, in this study, a new ventilation system was devised to improve indoor air quality and spatial homogeneity by installing ventilation inlets on the ceiling and numerous outlets on the floor, creating a vertical airflow in the interior space; this system was then applied to a middle school classroom. Using the age of air as an index, air quality improvement between the existing and newly designed ventilation systems was compared. In the classroom with the existing ventilation system, the age of air was low in the area near the ventilation inlets, while air congestion areas were widely distributed and air age was high near the outlets. Conversely, in the vertical airflow classroom, the average age of air was approximately 15% lower than that with the existing ventilation system, and the deviation of air age for each position in the classroom space was also reduced, showing a uniform air age distribution. Therefore, the vertical airflow ventilation system proposed in this study can be an effective ventilation scheme for enhancing and homogenizing indoor air quality.
Files in This Item
Appears in
Collections
서울 공과대학 > 서울 기계공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Yook, Se Jin photo

Yook, Se Jin
COLLEGE OF ENGINEERING (SCHOOL OF MECHANICAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE