Energy advantage of cold energy recovery system using water- and air-side free cooling technologies in semiconductor fabrication plant in summer

Authors
Kwon, Taek-DonJeong, Jae-Weon
Issue Date
Jun-2023
Publisher
ELSEVIER
Keywords
Semiconductor fabrication plant; Water-side free cooling; Air-side free cooling; Outdoor air-conditioner; Cold energy recovery
Citation
JOURNAL OF BUILDING ENGINEERING, v.69, pp.1 - 21
Indexed
SCIE
SCOPUS
Journal Title
JOURNAL OF BUILDING ENGINEERING
Volume
69
Start Page
1
End Page
21
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/189592
DOI
10.1016/j.jobe.2023.106277
Abstract
The semiconductor industry requires large amounts of energy. Of the total energy, semiconductor manufacturing facilities consume the most electricity, where 21–29% of the total energy is used to maintain a clean room environment at a constant temperature and humidity. The energy required for constant temperature and humidity has been developed and applied in various ways, e.g., waste heat recovery technology without a boiler. However, it is highly difficult to obtain the energy required for cooling without operating a chiller unless there is a climatic advantage. Therefore, with the perspective of introducing cold energy recovery system into outdoor air-conditioner, this paper suggests the analysis of the energy-saving effect of the recovery system which recovers wasted cold energy of the exhaust gas from the semiconductor fabrication plant located in high-temperature and humid region. Two systems have been proposed: a water-side free cooling system that recovers cold energy by connecting a cooling tower to exhaust gas, and an air-side free cooling system that recovers cold energy by connecting a membrane energy heat exchanger. When applied to the conventional outdoor air-conditioner after cold energy recovery in both systems, the energy-saving effect was estimated by a simulation program (i.e., engineer equation solver) using a theoretical calculation model. The result showed that the cooling load of the outdoor air-conditioner decreased by 10.2–13.1% and 8.5–11.2% when the water-side free cooling system and air-side free cooling system, respectively, were applied at an exhaust gas temperature of 24–28 °C and a humidity ratio of 0.00733 kg/kg’. However, with the consideration of the power consumed by the cold energy recovery system (i.e., water/air-side free cooling system), actual energy-saving rate was low. Consequently, the head and static pressure designs of the fluid transfer equipment (i.e., pumps and fans) of the cold energy recovery system should be considered with caution when the cold energy recovery system is applied.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE