Multi-objective optimization for capacity matching and energy performance of heat-pump-driven liquid-desiccant air-conditioning system

Authors
Lee, Jae-HeeCheon, Seong-YongJeong, Jae-Weon
Issue Date
Jul-2023
Publisher
Elsevier Ltd
Keywords
Capacity matching; Energy performance; Heat pump; Liquid desiccant; Multi-objective optimization
Citation
Applied Thermal Engineering, v.229, pp.1 - 14
Indexed
SCIE
SCOPUS
Journal Title
Applied Thermal Engineering
Volume
229
Start Page
1
End Page
14
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/191726
DOI
10.1016/j.applthermaleng.2023.120615
ISSN
1359-4311
Abstract
In heat-pump-driven liquid-desiccant (HPLD) air-conditioning systems, releasing condensing heat from heat pump to regenerator solution and exhaust air (i.e., capacity matching) is important for maintaining dehumidification performance, operational feasibility, and system stability. Therefore, this study optimizes capacity matching, especially focusing on releasing extra condensing heat, which has simply been assumed to be well-treated in previous studies, in conjunction with energy performance. With four design variables under various outdoor air conditions, a multi-objective optimization is conducted to simultaneously maximize system coefficient of performance (COP) and minimize a newly defined capacity-matching index of extra condenser. Pareto front, a set of optimum points, is obtained using a multi-objective genetic algorithm. Final optimum solutions are then determined and discussed based on a decision-making scenario. In optimization results, the regenerator air and solution flow rates should be respectively greater and lower than those of the absorber. The optimum temperature of absorber inlet solution is generally distributed at approximately 18 °C, while that of regenerator inlet solution is significantly influenced by the decision-making scenario. Finally, the system COP was maximally increased by 24 %, and the capacity-matching index of extra condenser was maximally decreased by 55 %, compared with each initial value.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE