Cited 0 time in
Applicability of a dedicated outdoor air system assisted by isothermal dehumidification and evaporative cooling
| DC Field | Value | Language |
|---|---|---|
| dc.contributor.author | Cheon, Seong-Yong | - |
| dc.contributor.author | Cho, Hye-Jin | - |
| dc.contributor.author | Jeong, Jae-Weon | - |
| dc.date.accessioned | 2023-12-11T07:31:29Z | - |
| dc.date.available | 2023-12-11T07:31:29Z | - |
| dc.date.issued | 2024-04 | - |
| dc.identifier.issn | 2352-7102 | - |
| dc.identifier.issn | 2352-7102 | - |
| dc.identifier.uri | https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/193247 | - |
| dc.description.abstract | A dedicated outdoor air system (DOAS) assisted by an isothermal dehumidifier and an indirect evaporative cooler is proposed, and its energy-saving potential is evaluated based on detailed simulations. In the proposed system, an isothermal dehumidifier accommodates the latent cooling load and an indirect evaporative cooler assumes a sensible cooling load. The energy performance of the proposed system was evaluated by comparing it with two conventional dedicated outdoor air systems: a DOAS with a desiccant wheel and a DOAS with a cooling coil. The results indicate that the proposed DOAS can accommodate sensible and latent cooling loads, but it consumes 10% more operating energy because of the low coefficient of performance (COP) (0.67) of the isothermal dehumidifier, despite the free cooling operation by the indirect evaporative cooler. For comparable energy performance, the proposed system requires the COP of the isothermal dehumidifier to be greater than 0.78, which is achieved through improvements in the membrane selectivity and vacuum pump (compression ratio and isentropic efficiency). | - |
| dc.format.extent | 20 | - |
| dc.language | 영어 | - |
| dc.language.iso | ENG | - |
| dc.publisher | Elsevier BV | - |
| dc.title | Applicability of a dedicated outdoor air system assisted by isothermal dehumidification and evaporative cooling | - |
| dc.type | Article | - |
| dc.publisher.location | 네델란드 | - |
| dc.identifier.doi | 10.1016/j.jobe.2023.108169 | - |
| dc.identifier.scopusid | 2-s2.0-85178021747 | - |
| dc.identifier.wosid | 001126049100001 | - |
| dc.identifier.bibliographicCitation | Journal of Building Engineering, v.82, pp 1 - 20 | - |
| dc.citation.title | Journal of Building Engineering | - |
| dc.citation.volume | 82 | - |
| dc.citation.startPage | 1 | - |
| dc.citation.endPage | 20 | - |
| dc.type.docType | Article | - |
| dc.description.isOpenAccess | N | - |
| dc.description.journalRegisteredClass | scie | - |
| dc.description.journalRegisteredClass | scopus | - |
| dc.relation.journalResearchArea | Construction & Building Technology | - |
| dc.relation.journalResearchArea | Engineering | - |
| dc.relation.journalWebOfScienceCategory | Construction & Building Technology | - |
| dc.relation.journalWebOfScienceCategory | Engineering, Civil | - |
| dc.subject.keywordPlus | Air conditioning | - |
| dc.subject.keywordPlus | Coefficient of performance | - |
| dc.subject.keywordPlus | Cooling | - |
| dc.subject.keywordPlus | Driers (materials) | - |
| dc.subject.keywordPlus | Evaporation | - |
| dc.subject.keywordPlus | Humidity control | - |
| dc.subject.keywordPlus | Isotherms | - |
| dc.subject.keywordAuthor | Dedicated outdoor air system | - |
| dc.subject.keywordAuthor | Energy simulation | - |
| dc.subject.keywordAuthor | Indirect evaporative cooler | - |
| dc.subject.keywordAuthor | Isothermal dehumidifier | - |
| dc.identifier.url | https://www.sciencedirect.com/science/article/pii/S2352710223023495?via%3Dihub | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
222, Wangsimni-ro, Seongdong-gu, Seoul, 04763, Korea+82-2-2220-1366
COPYRIGHT © 2024 HANYANG UNIVERSITY.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.