Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Enhancement of Indoor Air Quality with a Displacement Ventilation System Comprising a 4-Way Fan Coil Unit and Multiple Air Purifiersopen access

Authors
Park, Su-HoonAn, Ik-HyunLee, Yong-HoCho, Sang-HyunLee, Chang-HoonSeo, Sang-BumLee, Hyun-WooYook, Se-Jin
Issue Date
Mar-2024
Publisher
MDPI Open Access Publishing
Keywords
4-way fan coil unit; age of air; air purifier; displacement ventilation; indoor air quality
Citation
Sustainability, v.16, no.5, pp 1 - 17
Pages
17
Indexed
SCIE
SSCI
SCOPUS
Journal Title
Sustainability
Volume
16
Number
5
Start Page
1
End Page
17
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/198075
DOI
10.3390/su16051740
ISSN
2071-1050
2071-1050
Abstract
In indoor spaces without mechanical ventilation systems, a common approach involves using a ceiling-mounted 4-way fan coil unit (4WFCU) to regulate indoor temperature and placing floor-level air purifiers (APs) to remove indoor pollutants. This study introduces a differentiated displacement ventilation system (DVS) that connects multiple APs to the 4WFCU using ductwork. The age of air was compared between the case where the newly designed DVS was implemented and the reference case where 4WFCU and APs operated independently. When there were no obstacles in the office central area, the reference system exhibited a lower age of air. Conversely, when obstacles such as desks and partitions were present in the central area, the proposed DVS was found to improve indoor air quality. The DVS resulted in minimal interference among pathlines of the air discharged from multiple floor-level APs and their efficient suction through the ceiling-mounted 4WFCU and diffusers, significantly reducing stagnant air zones, while pathlines of the air discharged from the 4WFCU and APs interfered significantly when they operated independently, leading to larger stagnant areas in the air distribution. Therefore, modifying office spaces with ceiling-mounted 4WFCUs using the proposed DVS is anticipated to substantially enhance indoor air quality through a straightforward installation process.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 기계공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Yook, Se Jin photo

Yook, Se Jin
COLLEGE OF ENGINEERING (SCHOOL OF MECHANICAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE