Evaluation of clean air delivery rates and operating cost effectiveness for room air cleaner and ventilation system in a small lecture room

Authors
Noh, Kwang-ChulYook, Se-Jin
Issue Date
May-2016
Publisher
Elsevier BV
Keywords
Air cleaner; Clean air delivery rate (CADR); Operating cost effectiveness; Particle; Ventilation
Citation
Energy and Buildings, v.119, pp 111 - 118
Pages
8
Indexed
SCIE
SCOPUS
Journal Title
Energy and Buildings
Volume
119
Start Page
111
End Page
118
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/2564
DOI
10.1016/j.enbuild.2016.03.027
ISSN
0378-7788
1872-6178
Abstract
In general, room air cleaners are rated according to clean air delivery rate (CADR). However, ventilation systems have not yet been assessed using a metric similar to CADR. This study establishes a new mass balance equation that compares the CADRs of a ventilation system and a room air cleaner. Experiments and CFD simulations were conducted to evaluate and compare the CADRs of room air cleaners and ventilation system in the view of removing particles from indoor air. In addition, the operating cost effectiveness of ventilation system and room air cleaner was investigated. The results showed that the room air cleaners showed their performance independently, even when two or more room air cleaners were operated simultaneously. In the ventilation system, an air filter with MERV11 or higher rating was recommended to reduce the indoor particle concentration when 100% outdoor air was supplied. It was possible to select an air filter with MERV11 or lower rating when the recirculation airflow rate was increasing up to 70%. The CADR of the room air cleaner was higher than that of the ventilation system regardless of the particle size and the filter performance when the airflow rate was same. The operating cost effectiveness (CADR/kW) of the room air cleaner was higher than that of the ventilation system at the same airflow rate. Therefore, the room air cleaner must be more cost-effective than the ventilation system for reducing particle concentration indoors. (C) 2016 Elsevier B.V. All rights reserved.
Files in This Item
There are no files associated with this item.
Appears in
Collections
서울 공과대학 > 서울 기계공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Yook, Se Jin photo

Yook, Se Jin
COLLEGE OF ENGINEERING (SCHOOL OF MECHANICAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE