Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

에너지비용변화에 따른 경제적 단위마찰저항 값에 대한 고찰A Study of the Friction Factor Unit Considering the Cost of Energy

Other Titles
A Study of the Friction Factor Unit Considering the Cost of Energy
Authors
신동신김아인이병현정형목이성구
Issue Date
2016
Publisher
대한설비공학회
Keywords
Pipe(배관); Frictional resistance(마찰저항); Energy cost(에너지비용); Office building(사무용 건물); Hazen-Williams equation(하겐-윌리엄즈 방정식)
Citation
설비공학 논문집, v.28, no.1, pp.29 - 34
Journal Title
설비공학 논문집
Volume
28
Number
1
Start Page
29
End Page
34
URI
https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/13443
DOI
10.6110/KJACR.2016.28.1.029
ISSN
1229-6422
Abstract
The friction factor unit was studied to find a more economic alternative compared to the conventional 30 mmAq/m. The pipe and pump for cooling water piping used in a failing were selected, and the friction factor unit was changed to calculate the pipe diameter and the brake shaft power. Based on current electric charges, After the brake shaft power was converted into operational costs based on current electric charges, then an economic analysis was conducted considering that incorporated the initial installation costs and operational costs for the pump. We found that the friction factor unit when using 20 mmAq/m is more economical than that with 30 mmAq/m, if the piping is used for more than 4 years. The small friction factor unit is desirable when the piping is used for quite a long period of time, and the selection of a more economic friction factor unit should considering the period of usage will be important.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > Department of Mechanical and System Design Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Altmetrics

Total Views & Downloads

BROWSE