배전계통에서 1선 지락고장 시험에 의한 지락고장전류 분류에 관한 연구
DC Field | Value | Language |
---|---|---|
dc.contributor.author | 김경철 | - |
dc.contributor.author | 유창훈 | - |
dc.date.accessioned | 2021-11-11T06:41:23Z | - |
dc.date.available | 2021-11-11T06:41:23Z | - |
dc.date.created | 2021-11-10 | - |
dc.date.issued | 2013 | - |
dc.identifier.issn | 1229-4691 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/17724 | - |
dc.description.abstract | Phase to ground faults are possibly one of the maximum number of faults in power distribution system. During a ground fault the maximum fault current and neutral to ground voltage will appear at the pole nearest to the fault. Distribution lines are consisted of three phase conductors, an overhead ground wire and a multigrounded neutral line. In this paper phase to neutral faults were staged at the specified concrete pole along the distribution line and measured the ground fault current distribution in the ground fault current, three poles nearest to the fault point, overhead ground wire and neutral line. A simplified equivalent circuit model for the distribution system under case study calculated by using MATLAB gives results very close to the ground fault current distribution yielded by field tests. | - |
dc.language | 한국어 | - |
dc.language.iso | ko | - |
dc.publisher | 한국조명.전기설비학회 | - |
dc.title | 배전계통에서 1선 지락고장 시험에 의한 지락고장전류 분류에 관한 연구 | - |
dc.title.alternative | A Study on the Ground Fault Current Distribution by Single Phase-to-Neutral Fault Tests in Power Distribution System | - |
dc.type | Article | - |
dc.contributor.affiliatedAuthor | 김경철 | - |
dc.identifier.bibliographicCitation | 조명.전기설비학회논문지, v.27, no.7, pp.37 - 44 | - |
dc.relation.isPartOf | 조명.전기설비학회논문지 | - |
dc.citation.title | 조명.전기설비학회논문지 | - |
dc.citation.volume | 27 | - |
dc.citation.number | 7 | - |
dc.citation.startPage | 37 | - |
dc.citation.endPage | 44 | - |
dc.type.rims | ART | - |
dc.identifier.kciid | ART001789923 | - |
dc.description.journalClass | 2 | - |
dc.description.journalRegisteredClass | kci | - |
dc.subject.keywordAuthor | Phase to Neutral Fault | - |
dc.subject.keywordAuthor | Ground Fault Current Distribution | - |
dc.subject.keywordAuthor | Three-Phase Four-Wire Multigrounded Neutral Distribution System | - |
dc.subject.keywordAuthor | Artificial Fault Generator | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
94, Wausan-ro, Mapo-gu, Seoul, 04066, Korea02-320-1314
COPYRIGHT 2020 HONGIK UNIVERSITY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.