배전계통에서 1선 지락고장 시험에 의한 지락고장전류 분류에 관한 연구A Study on the Ground Fault Current Distribution by Single Phase-to-Neutral Fault Tests in Power Distribution System

Other Titles
A Study on the Ground Fault Current Distribution by Single Phase-to-Neutral Fault Tests in Power Distribution System
Authors
김경철유창훈
Issue Date
2013
Publisher
한국조명.전기설비학회
Keywords
Phase to Neutral Fault; Ground Fault Current Distribution; Three-Phase Four-Wire Multigrounded Neutral Distribution System; Artificial Fault Generator
Citation
조명.전기설비학회논문지, v.27, no.7, pp.37 - 44
Journal Title
조명.전기설비학회논문지
Volume
27
Number
7
Start Page
37
End Page
44
URI
https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/17724
ISSN
1229-4691
Abstract
Phase to ground faults are possibly one of the maximum number of faults in power distribution system. During a ground fault the maximum fault current and neutral to ground voltage will appear at the pole nearest to the fault. Distribution lines are consisted of three phase conductors, an overhead ground wire and a multigrounded neutral line. In this paper phase to neutral faults were staged at the specified concrete pole along the distribution line and measured the ground fault current distribution in the ground fault current, three poles nearest to the fault point, overhead ground wire and neutral line. A simplified equivalent circuit model for the distribution system under case study calculated by using MATLAB gives results very close to the ground fault current distribution yielded by field tests.