냉복도 밀폐시스템을 적용한 서버실의 실내온도조건Server Room Temperature Condition in Data Center with Cold Aisle Containment System
- Other Titles
- Server Room Temperature Condition in Data Center with Cold Aisle Containment System
- Authors
- 정용호; 장현재; 서장후
- Issue Date
- 2013
- Publisher
- 대한설비공학회
- Keywords
- Cold aisle containment system(냉복도 밀폐시스템); Recirculation air(재순환공기); Inlet temperature(흡입온도); Energy saving(에너지절감)
- Citation
- 설비공학 논문집, v.25, no.2, pp.79 - 84
- Journal Title
- 설비공학 논문집
- Volume
- 25
- Number
- 2
- Start Page
- 79
- End Page
- 84
- URI
- https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/18015
- DOI
- 10.6110/KJACR.2013.25.2.079
- ISSN
- 1229-6422
- Abstract
- In this study, a cold aisle containment system was proposed among various strategies to reduce the energy waste by recirculation air from the hot aisle. To verify the effectiveness of the cold aisle containment system, a test bed which is similar to an actually existing server room was set up in the Internet Data Center(IDC) building. Comparative experiments, conventional open type cooling system and cold aisle containment system were carried out under actual conditions. The result revealed that the range of inlet temperature of the server system was 20~ 25℃ in an existing cooling system and the range of inlet temperature dropped below 20℃ by the cold aisle containment system. After all, cold aisle containment system was proved to be the solution for energy saving cooling system.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - College of Science and Technology > Major in Architecture Engineering > 1. Journal Articles
![qrcode](https://api.qrserver.com/v1/create-qr-code/?size=55x55&data=https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/18015)
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.