가공지선이 연결된 송전철탑의 탑각저항 측정에 관한 연구A Study on the Measurement of Footing Resistance of Transmission Towers with Overhead Grounding wires

Other Titles
A Study on the Measurement of Footing Resistance of Transmission Towers with Overhead Grounding wires
Authors
이원교최종기이영우최인혁김경철
Issue Date
2010
Publisher
한국전기전자재료학회
Keywords
Footing resistance; Ground resistance; Back-flashover
Citation
전기전자재료학회논문지, v.23, no.1, pp.61 - 64
Journal Title
전기전자재료학회논문지
Volume
23
Number
1
Start Page
61
End Page
64
URI
https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/21561
ISSN
1226-7945
Abstract
Footing Resistance of a 154 kV transmission towers in korea is commonly required to be less than 15 ohm to avoid lightning back-flashover accident. The periodic measurement of Footing Resistance is important to verify that the grounding performance of the towers has been maintained good. Towers are electrically connected in parallel with overhead grounding wire, therefore footing resistance of each tower will be measured after disconnecting the overhead ground wires from the towers. however, In this paper, three direct measurement methods of footing resistance are presented. There are very useful methods without disconnecting overhead ground wires from the tower under measurement. They are compared in KEPCO 154 kV transmission towers. The experimental results describe performances of them.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Science and Technology > Department of Electronic and Electrical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Altmetrics

Total Views & Downloads

BROWSE