Abstract
비록 접지저항은 접지전극의 접지성능을 좌우하는 지수이기는 하지만, 과도상태에서는 접지 성능을 반영하지 못한다. 동봉은 배전계통에서 가장 많이 쓰이는 접지전극이다. 본 논문에서는 동봉의 접지 임피던스를 주파수 60[㎐]에서 100[㎑] 범위까지 측정하여 등가 접지임피던스 모델을 구하였다. 뇌격서지가 유입되었을 때 MATLAB 프로그램으로 과도접지임피던스의 수치와 파형을 시뮬레이션하였다.