Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

공동주택용 폐열회수형 환기장치의성능에 관한 측정 연구A Study on the Performance of Heat RecoveryVentilators for Apartment Houses

Other Titles
A Study on the Performance of Heat RecoveryVentilators for Apartment Houses
Authors
장현재홍석진
Issue Date
2008
Publisher
대한설비공학회
Keywords
Heat recovery ventilator(폐열회수 환기장치); Fan performance(팬 풍량-정압 특성); Air leakage(누기율); Heat exchange efficiency(열교환 효율)
Citation
설비공학 논문집, v.20, no.1, pp.26 - 34
Journal Title
설비공학 논문집
Volume
20
Number
1
Start Page
26
End Page
34
URI
https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/23389
ISSN
1229-6422
Abstract
Heat recovery ventilator(HRV) is recommended to improve indoor air quarlity (IAQ) and energy conservation in apartment houses. Recently, in Korea, HRV is produced from many manufacturers. However, there have been not so many experiences to apply HRV in apartment houses and verification on the performance such as heat exchange efficiency, carry-over rate, internal leakage, etc. have not been carried out sufficiently. So in this study, fan performance, heat exchange efficiency, air leakage, internal exhaust leakage, external leakage and sound level of HRV were examined for selected HRV models under domestic and international standard. Results of performance test, there were need to improve latent heat exchange efficiency and sound level of HRV.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Science and Technology > Major in Architecture Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Chang, Hyun jae photo

Chang, Hyun jae
Science & Technology (Architectural Engineering)
Read more