도심지 변전소 지락사고시 인근 저항성간섭 영향 해석Analysis of Conductive Interference Around Substation Exclusively Fed by Cables Under Ground Fault Condition

Other Titles
Analysis of Conductive Interference Around Substation Exclusively Fed by Cables Under Ground Fault Condition
Authors
최종기이동일김재준유연표정창수김경철
Issue Date
2005
Publisher
대한전기학회
Keywords
접지전류; 접지저항; 저항성간섭
Citation
전기학회논문지 A권, v.54, no.12-A, pp.592 - 596
Journal Title
전기학회논문지 A권
Volume
54
Number
12-A
Start Page
592
End Page
596
URI
https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/25347
ISSN
1229-2443
Abstract
- Recently, substations have been constructed in GIS (Gas Insulated Switchgear) and indoor type because of the increasing difficulties of securing locations. In case of urban substations, it is also common that the substations are exclusively fed by underground cables. Sometimes, the infrastructures in urban area, such as communication facilities, are located near substations to be constructed. In this paper, we examined such a case that a branch office building of KT(Korea Telecom) was located near 154 kV underground GIS substation under construction with about 100 meters of the lateral distance between two facilities. GPR (Ground Potential Rise) at the substation and the transferred earth potential at the KT building through the earth in SLG (Single-Line-to- Ground) fault condition were investigated based on a series of computer simulations. The calculated earth potential at a distance of 100 m from the substation was below 120 V which satisfying the limit value of 650 V.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Science and Technology > Department of Electronic and Electrical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Altmetrics

Total Views & Downloads

BROWSE