Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

암모니아-물 흡수식 냉각기의 동적 해석Dynamic Analysis of an Ammonia-Water Absorption Chiller

Other Titles
Dynamic Analysis of an Ammonia-Water Absorption Chiller
Authors
김병주
Issue Date
2004
Publisher
대한설비공학회
Keywords
Absorption system; Dynamic analysis; Bulk concentration; Charging ratio; Time constant; 흡수식 시스템; 동적 해석; 체적 농도; 충전비; 시간 상수
Citation
설비공학 논문집, v.16, no.10, pp.990 - 998
Journal Title
설비공학 논문집
Volume
16
Number
10
Start Page
990
End Page
998
URI
https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/26220
ISSN
1229-6422
Abstract
Dynamic behavior of an ammonia-water absorption system was investigated numerically. Thermal-hydraulic model for a single-effect 3 RT chiller was developed by applying transient conservation equations of total mass, NH3 mass, energy and momentum to each component. Transient variations of system properties and transport variables were analysed during start-up operation. Numerical analyses were performed to quantify the effects of bulk concentration and charging ratio on the system performance in terms of cooling capacity, coefficient of performance, and time constant of system. For an absorption chiller considered in the present study, optimum charging ratio and bulk concentration were to found to exist, which resulted in the maximum cooling capacity and COP. The time constant increased as the charging ratio increased, but decreased with the increase of bulk concentration.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > Department of Mechanical and System Design Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Altmetrics

Total Views & Downloads

BROWSE