Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Development of The Passive Air Mixing Chamber for an Air Handling Unit

Authors
Lim, SeokyoungChang, Hyunjae
Issue Date
2018
Publisher
IEEE
Keywords
air mixing chamber; air mixing ratio; air handling unit (AHU); pressure loss
Citation
2018 3RD INTERNATIONAL CONFERENCE ON SMART AND SUSTAINABLE TECHNOLOGIES (SPLITECH), pp.266 - 271
Journal Title
2018 3RD INTERNATIONAL CONFERENCE ON SMART AND SUSTAINABLE TECHNOLOGIES (SPLITECH)
Start Page
266
End Page
271
URI
https://scholarworks.bwise.kr/hongik/handle/2020.sw.hongik/28127
Abstract
Air mixing chamber in an air handling unit (AHU) is an important part to affect heat exchange efficiency and the controllability of AHU. In this study, the novel definition of air mixing ratio (AMR) is proposed, and several ideas to improve AMR has been investigated by computational fluid dynamics (CFD) simulation and experiment. In conventional air mixing chamber, airflow characteristics show that outdoor air flowing into the air mixing chamber is suppressed by a large volume of return air, and OA and RA are not mixed well. AMR of the conventional air chamber is quite low as 20 similar to 50%. Among the cases investigated in this study, the case "Double inducing chamber / three slits on each side walls" shows the best mixing state. AMR of this case shows about 80%, and pressure loss around 20 Pa. These performance results have been validated through a separate experiments.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Science and Technology > Major in Architecture Engineering > 1. Journal Articles