VAV 터미널 박스의 최소풍량 설정에 따른 실내 열환경 및 에너지 성능 분석The Analysis of Energy Performance and Thermal Comfort according to the Minimum Airflow of the VAV Terminal Box
- Other Titles
- The Analysis of Energy Performance and Thermal Comfort according to the Minimum Airflow of the VAV Terminal Box
- Authors
- 강수현; 조영흠
- Issue Date
- Mar-2011
- Publisher
- 한국건축친환경설비학회
- Keywords
- VAV terminal box; Indoor air quality(IAQ); minimum airflow; energy savings; VAV terminal box; Indoor air quality(IAQ); minimum airflow; energy savings; VAV 터미널 박스; 실내 공기질; 최소풍량; 에너지 절약
- Citation
- 한국건축친환경설비학회 논문집, v.5, no.3, pp 130 - 136
- Pages
- 7
- Journal Title
- 한국건축친환경설비학회 논문집
- Volume
- 5
- Number
- 3
- Start Page
- 130
- End Page
- 136
- URI
- https://scholarworks.bwise.kr/kumoh/handle/2020.sw.kumoh/27858
- ISSN
- 1976-6483
- Abstract
- The minimum airflow of VAV terminal boxes is a key factor for comfort, indoor air quality(IAQ) and energy cost. If the minimum airflow is not resonable, it would waste energy and make IAQ problems. A building simulation was conducted to evaluate the energy consumption and the IAQ according to the minimum airflow of the VAV terminal boxes. It was found that the 4.5% energy savings when reducing the minimum airflow as CASE 2. And CASE 1 did not satisfy the IAQ during the Winter. And there are the two factors(indoor load and IAQ) to decide the minimum airflow.