Development of a Terminal Control System with Variable Minimum Airflow Rate
- Authors
- Cho, Young-Hum
- Issue Date
- Nov-2012
- Publisher
- MDPI
- Keywords
- terminal control system; variable minimum airflow rate; energy consumption; thermal performance; control algorithms
- Citation
- ENERGIES, v.5, no.11, pp 4643 - 4664
- Pages
- 22
- Journal Title
- ENERGIES
- Volume
- 5
- Number
- 11
- Start Page
- 4643
- End Page
- 4664
- URI
- https://scholarworks.bwise.kr/kumoh/handle/2020.sw.kumoh/28133
- DOI
- 10.3390/en5114643
- ISSN
- 1996-1073
- Abstract
- A constant minimum airflow rate is used in conventional Single Duct Variable Air Volume Terminal Box control sequences. This control sequence can cause occupant discomfort or use excessive energy under partial load conditions. If the minimum airflow rate is higher than required; terminal boxes will have significantly more simultaneous heating and cooling; and AHUs will consume more fan power. Buildings will have indoor air quality problems if the minimum airflow rate is less than required. Many engineers and researchers have investigated advanced variable air volume terminal box control algorithms without a system retrofit for thermal comfort; indoor air quality and energy savings. In this study a developed control system with variable minimum airflow rate for Single Duct Variable Air Volume Terminal Boxes was applied and validated using an actual building and evaluated for comfort; indoor air quality and energy consumption. The energy consumption and thermal performance of terminal boxes using the conventional and proposed control algorithms were compared.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - ETC > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.