Temperature Characteristics Analysis of Hybrid Transformer하이브리드 몰드 변압기의 온도 특성 해석
- Other Titles
- 하이브리드 몰드 변압기의 온도 특성 해석
- Authors
- 김종왕; 박훈양; 이향범; 현동석; 심재명
- Issue Date
- Jul-2013
- Publisher
- Korean Institute of Electrical Engineers
- Keywords
- CFD; Hybrid transformer; Temperature characteristics analysis; Zig-zag connection
- Citation
- Transactions of the Korean Institute of Electrical Engineers, v.62, no.7, pp.931 - 936
- Journal Title
- Transactions of the Korean Institute of Electrical Engineers
- Volume
- 62
- Number
- 7
- Start Page
- 931
- End Page
- 936
- URI
- http://scholarworks.bwise.kr/ssu/handle/2018.sw.ssu/11809
- DOI
- 10.5370/KIEE.2013.62.7.931
- ISSN
- 1975-8359
- Abstract
- In this paper, the temperature distribution of 400kVA hybrid transformer is predicted by using CFD analysis.
The copper loss and iron loss which are heat source are calculated by using Joule heat and Bertotti's equation respectively. To improve the convergence of the numerical calculation and to reduce the computation time, the 1/4 model is used and the incompressible air model is used for external air. To verify analysis result, the temperature rise test and no-load test of the transformer are performed. The experiment result obtained by using thermo-graphic camera is similar to the numerical result of the CFD analysis.
- Files in This Item
-
Go to Link
- Appears in
Collections - College of Engineering > School of Electrical Engineering > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.