Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

콘크리트에 매입된 기초접지극의 크기 및 설치방법에 관한 고찰A Consideration of Volume and Installation Method of Concrete-Embedded Foundation Earthed an Electrode

Other Titles
A Consideration of Volume and Installation Method of Concrete-Embedded Foundation Earthed an Electrode
Authors
이주철이영철김재철
Issue Date
Jul-2013
Publisher
한국조명.전기설비학회
Keywords
Lightning Protection System; Concrete-Embedded Foundation Earth Electrode; Foundation Earth Electrode
Citation
조명.전기설비학회논문지, v.27, no.7, pp.82 - 88
Journal Title
조명.전기설비학회논문지
Volume
27
Number
7
Start Page
82
End Page
88
URI
http://scholarworks.bwise.kr/ssu/handle/2018.sw.ssu/11820
ISSN
1229-4691
Abstract
IEC standards do not require to limit the earthing resistance of the concrete-embedded foundation earthing electrode which is installed to a specific value. However, in Korea the value of 5Ω and below applies to the earthing resistance for a domestic customer whose receiving voltage is 22.9kV. This paper calculates the minimum area and volume of the concrete-embedded foundation earthing electrode in order to obtain a specific value of the earthing resistance when the electrode of the building's lightning protection system and that of its power system are interconnected. It also suggested the most appropriate method of installing the foundation earthing electrode, taking the electric characteristics of concrete into account.
Files in This Item
Go to Link
Appears in
Collections
College of Engineering > School of Electrical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Kim, Jae Chul photo

Kim, Jae Chul
College of Engineering (School of Electrical Engineering)
Read more

Altmetrics

Total Views & Downloads

BROWSE