콘크리트에 매입된 기초접지극의 크기 및 설치방법에 관한 고찰A Consideration of Volume and Installation Method of Concrete-Embedded Foundation Earthed an Electrode
- Other Titles
- A Consideration of Volume and Installation Method of Concrete-Embedded Foundation Earthed an Electrode
- Authors
- 이주철; 이영철; 김재철
- Issue Date
- Jul-2013
- Publisher
- 한국조명.전기설비학회
- Keywords
- Lightning Protection System; Concrete-Embedded Foundation Earth Electrode; Foundation Earth Electrode
- Citation
- 조명.전기설비학회논문지, v.27, no.7, pp.82 - 88
- Journal Title
- 조명.전기설비학회논문지
- Volume
- 27
- Number
- 7
- Start Page
- 82
- End Page
- 88
- URI
- http://scholarworks.bwise.kr/ssu/handle/2018.sw.ssu/11820
- ISSN
- 1229-4691
- Abstract
- IEC standards do not require to limit the earthing resistance of the concrete-embedded foundation earthing electrode which is installed to a specific value. However, in Korea the value of 5Ω and below applies to the earthing resistance for a domestic customer whose receiving voltage is 22.9kV. This paper calculates the minimum area and volume of the concrete-embedded foundation earthing electrode in order to obtain a specific value of the earthing resistance when the electrode of the building's lightning protection system and that of its power system are interconnected. It also suggested the most appropriate method of installing the foundation earthing electrode, taking the electric characteristics of concrete into account.