Improvement of Protection Coordination of Protective Devices Through Application of a SFCL in a Power Distribution System With a Dispersed Generation
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Lim, Sung-Hun | - |
dc.contributor.author | Kim, Jin-Seok | - |
dc.contributor.author | Kim, Myong-Hyon | - |
dc.contributor.author | Kim, Jae-Chul | - |
dc.date.available | 2018-05-10T05:19:35Z | - |
dc.date.created | 2018-04-17 | - |
dc.date.issued | 2012-06 | - |
dc.identifier.issn | 1051-8223 | - |
dc.identifier.uri | http://scholarworks.bwise.kr/ssu/handle/2018.sw.ssu/12416 | - |
dc.description.abstract | The introduction of various dispersed generation (DG) in a power distribution system has caused the short-circuit current to increase, which can make the operation of the protective device deviate from its original set value. Especially, the increase of a short-circuit current in a power distribution system due to the increase of the DG is expected to be required for the related power utilities such as the circuit breaker to be replaced with a larger one. Among the countermeasures to solve the short-circuit problem in a power distribution system considering the increase of the DG, the superconducting fault current limiter (SFCL) has been noticed as one of the promising devices. In this paper, the protection coordination of the protective devices due to the application of a SFCL in a power distribution system where the DG was introduced into its bus line was analysed. The experimental circuit to simulate the DG and the protective devices was designed and realized by using power electronic switches. The short-circuit tests for the power distributed system assembled with the DG, the protective devices and the SFCL were carried out. Through the analysis on the results from the short-circuit tests, the application of the SFCL with its proper resistance amplitude in a power distribution system with the DG could be confirmed to be contributed to the improvement of the protection coordination of the protective devices. | - |
dc.publisher | IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC | - |
dc.relation.isPartOf | IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY | - |
dc.title | Improvement of Protection Coordination of Protective Devices Through Application of a SFCL in a Power Distribution System With a Dispersed Generation | - |
dc.type | Article | - |
dc.identifier.doi | 10.1109/TASC.2011.2181930 | - |
dc.type.rims | ART | - |
dc.identifier.bibliographicCitation | IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, v.22, no.3 | - |
dc.description.journalClass | 1 | - |
dc.identifier.wosid | 000307364700386 | - |
dc.identifier.scopusid | 2-s2.0-84862552433 | - |
dc.citation.number | 3 | - |
dc.citation.title | IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY | - |
dc.citation.volume | 22 | - |
dc.contributor.affiliatedAuthor | Lim, Sung-Hun | - |
dc.contributor.affiliatedAuthor | Kim, Jae-Chul | - |
dc.type.docType | Article; Proceedings Paper | - |
dc.subject.keywordAuthor | Dispersed generation (DG) | - |
dc.subject.keywordAuthor | protection coordination | - |
dc.subject.keywordAuthor | protective device | - |
dc.subject.keywordAuthor | short-circuit current | - |
dc.subject.keywordAuthor | superconducting fault current limiter (SFCL) | - |
dc.description.journalRegisteredClass | scie | - |
dc.description.journalRegisteredClass | scopus | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
Soongsil University Library 369 Sangdo-Ro, Dongjak-Gu, Seoul, Korea (06978)02-820-0733
COPYRIGHT ⓒ SOONGSIL UNIVERSITY, ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.