Detailed Information

Cited 0 time in webofscience Cited 30 time in scopus
Metadata Downloads

Parameter Optimization of SFCL With Wind-Turbine Generation System Based on Its Protective Coordination

Authors
Park, Woo-JaeSung, Byung ChulSong, Kyung-BinPark, Jung-Wook
Issue Date
Jun-2011
Publisher
IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC
Keywords
Equivalent voltage source method; overcurrent relay; protective coordination; short-circuit current; superconducting fault current limiter; wind-turbine generation system
Citation
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, v.21, no.3, pp.2153 - 2156
Journal Title
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY
Volume
21
Number
3
Start Page
2153
End Page
2156
URI
http://scholarworks.bwise.kr/ssu/handle/2018.sw.ssu/13650
DOI
10.1109/TASC.2010.2090855
ISSN
1051-8223
Abstract
This paper describes a study to determine the optimal resistance of a superconducting fault current limiter (SFCL) connected to a wind-turbine generation system (WTGS) in series considering its protective coordination. The connection of the WTGS to the electric power grid may have serious effects on the stability and reliability of the overall system during a contingency due to the increase in fault currents. Moreover, it causes malfunction in the protective devices such as overcurrent relays (OCRs). To deal with this problem, the SFCL is applied to reduce the level of fault current increased by the connection of the WTGS. Then, to determine the optimal parameter of the SFCL, protective coordination between the existing multiple OCRs is considered based on the computation of fault current by the equivalent voltage source method. The effectiveness of the optimal resistance for the SFCL is evaluated by the time-domain simulation with the power systems computer aided design/electromagnetic transients including DC (PSCAD/EMTDC) software. The results show that protective coordination is well maintained without changing the previous settings of existing OCRs by applying the SFCL with its optimal parameter. Therefore, the system can keep its suitable reliability even when the level of fault current is increased by connecting the WTGS to the power system.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > School of Electrical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Song, Kyung Bin photo

Song, Kyung Bin
College of Engineering (School of Electrical Engineering)
Read more

Altmetrics

Total Views & Downloads

BROWSE