Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

직류전원을 이용한 배전급 차단기의 등가 3상 합성투입시험법Equivalent three-phase synthetic making test for medium voltage circuit breaker of distribution system using DC power

Other Titles
Equivalent three-phase synthetic making test for medium voltage circuit breaker of distribution system using DC power
Authors
박병락조만영김진석신희상김재철
Issue Date
Jul-2011
Publisher
한국조명.전기설비학회
Keywords
Short-Circuit Generator; Synthetic Making Test; Medium Voltage Circuit Breaker; Pre-Arc; DC Power
Citation
조명.전기설비학회논문지, v.25, no.7, pp.105 - 113
Journal Title
조명.전기설비학회논문지
Volume
25
Number
7
Start Page
105
End Page
113
URI
http://scholarworks.bwise.kr/ssu/handle/2018.sw.ssu/14016
ISSN
1229-4691
Abstract
The study about three-phase synthetic making test using DC power has been performed in order to increase the making test capacity on Vacuum Circuit Breaker. And, it made possible to solve the limitations that short-circuit testing facilities can not fulfill the testing requirements of VCB exceeding three-phase 36[kV] 31.5[kA]. By using DC power and high speed spark-gap switch, this method made the equivalence with the pre-arc that occurred during the making process under the fault condition of power system. As results, KERI(Korea Electrotechnology Research Institute) could have capacity to carry out type test for VCB under three-phase 52[kV] 40[kV], which satisfies the IEC Standard.
Files in This Item
Go to Link
Appears in
Collections
College of Engineering > School of Electrical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Kim, Jae Chul photo

Kim, Jae Chul
College of Engineering (School of Electrical Engineering)
Read more

Altmetrics

Total Views & Downloads

BROWSE