제한된 부지에서 위험전압 검토에 의한 메시 접지설계Mesh Grounding Design Based on the Study of Dangerous Voltage on Limited Sites
- Other Titles
- Mesh Grounding Design Based on the Study of Dangerous Voltage on Limited Sites
- Authors
- 손석금; 김재철
- Issue Date
- Nov-2011
- Publisher
- 한국조명.전기설비학회
- Keywords
- Dangerous Voltage; Mesh Grounding; Grounding Design; Dangerous Voltage; Mesh Grounding; Grounding Design
- Citation
- 조명.전기설비학회논문지, v.25, no.11, pp.91 - 97
- Journal Title
- 조명.전기설비학회논문지
- Volume
- 25
- Number
- 11
- Start Page
- 91
- End Page
- 97
- URI
- http://scholarworks.bwise.kr/ssu/handle/2018.sw.ssu/14234
- ISSN
- 1229-4691
- Abstract
- In Korea, characterized in most cases by limited area or high earth resistivity, it is likely to design narrow distances between grounding conductors, with a view to keeping ground resistance and touch voltage below the safety margin values.
A new grounding method is suggested, making use of double meshes, to lower touch voltage in a confined area, since it is difficult to lay the plugs under the ground with narrow gaps between them on a limited site.
For the presentation of a new model, the suggested grounding system has been analyzed and studied in ground resistance, touch voltage and step voltage, using IEEE Std. 80 calculations and computer simulations.