Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

다수의 냉각탑이 설치된 옥상에서 냉각탑별 재유입률 예측

Full metadata record
DC Field Value Language
dc.contributor.author이태구-
dc.contributor.author문선애-
dc.contributor.author유호선-
dc.contributor.author이재헌-
dc.date.available2018-05-10T17:26:28Z-
dc.date.created2018-04-17-
dc.date.issued2006-11-
dc.identifier.issn1229-6422-
dc.identifier.urihttp://scholarworks.bwise.kr/ssu/handle/2018.sw.ssu/19055-
dc.description.abstractIn this paper, reentering ratio and cooling capacity of individual cooling towers arrayed on a building roof were studied by a numerical method. The number of 16 cooling towers were divided into 4 banks. It was considered the summer prevailing wind characteristics as west wind and south wind of 5m/s. It was also considered the roofwall types as the curtainwall and the louverwall that had the outdoor air intake louver in the curtainwall. In this case, the louver was suggested as the solution that could prevent reentering phenomenon due to recirculation and interference of the discharge air. In the case of the curtainwall, the averaged reentering ratio are predicted 13.3% and 24.4% for the west and south wind of 5 m/s, respectively. In the case of the louverwall, the averaged reentering ratio are predicted 2.5% and 9.7% for the west and south wind of 5m/s, respectively. Therefore, the louverwall is a appropriate solution for reducing the reentering phenomenon.-
dc.language한국어-
dc.language.isoko-
dc.publisher대한설비공학회-
dc.relation.isPartOf설비공학 논문집-
dc.subjectCooling tower(냉각탑)-
dc.subjectRecirculation(재순환)-
dc.subjectInterference(간섭)-
dc.subjectReentering rate(재유입률)-
dc.title다수의 냉각탑이 설치된 옥상에서 냉각탑별 재유입률 예측-
dc.title.alternativePrediction of Reentering Ratio of Individual Cooling Towers Scatteredon a Building Roof-
dc.typeArticle-
dc.type.rimsART-
dc.identifier.bibliographicCitation설비공학 논문집, v.18, no.11, pp.923 - 932-
dc.identifier.kciidART001026919-
dc.description.journalClass2-
dc.citation.endPage932-
dc.citation.number11-
dc.citation.startPage923-
dc.citation.title설비공학 논문집-
dc.citation.volume18-
dc.contributor.affiliatedAuthor유호선-
dc.identifier.urlhttps://www.kci.go.kr/kciportal/ci/sereArticleSearch/ciSereArtiView.kci?sereArticleSearchBean.artiId=ART001026919-
dc.description.isOpenAccessN-
dc.subject.keywordAuthorCooling tower(냉각탑)-
dc.subject.keywordAuthorRecirculation(재순환)-
dc.subject.keywordAuthorInterference(간섭)-
dc.subject.keywordAuthorReentering rate(재유입률)-
dc.description.journalRegisteredClasskci-
Files in This Item
Go to Link
Appears in
Collections
College of Engineering > ETC > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Yoo, Ho seon photo

Yoo, Ho seon
College of Engineering (School of Mechanical Engineering)
Read more

Altmetrics

Total Views & Downloads

BROWSE