Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

복합면진장치를 적용한 무정전전원장치의 1축 진동대실험 기반 동적특성 분석Dynamic Characteristic of the Seismic Performance of Uninterruptible Power Supply with Combined Isolator Using Shaking Table Test

Other Titles
Dynamic Characteristic of the Seismic Performance of Uninterruptible Power Supply with Combined Isolator Using Shaking Table Test
Authors
이지언이승재박원일최경규
Issue Date
Feb-2022
Publisher
한국구조물진단유지관리공학회
Keywords
무정전전원장치; 복합면진장치; 고감쇠고무; 진동대실험; 동적특성; 가속도 시간이력; Uninterruptible power supply; Combined isolator; High damping rubber bearing; Shaking table test; Dynamic characteristics; Acceleration time history response
Citation
한국구조물진단유지관리공학회 논문집, v.26, no.1, pp.19 - 28
Journal Title
한국구조물진단유지관리공학회 논문집
Volume
26
Number
1
Start Page
19
End Page
28
URI
http://scholarworks.bwise.kr/ssu/handle/2018.sw.ssu/42239
DOI
10.11112/jksmi.2022.26.1.19
ISSN
2234-6937
Abstract
본 연구에서는 전력·통신 설비로 분류되는 무정전전원장치의 내진성능을 향상하기 위하여 고감쇠고무와 와이어 면진장치를 결합한 3가지 유형의 복합면진장치를 개발하였다. 복합면진장치를 적용한 UPS의 동적 특성을 분석하기 위하여 단축 진동대 실험을 수행하였다. 진동대 실험은 국외 진동대 실험 기준인 ICC-ES AC156을 따라 수행하였으며 기준에서 제시하고 있는 요구응답스텍트럼을 기반으로 입력 지진파를 생성하였다. 입력 지진파의 스케일을 50%에서 200%까지 증가시키며 가진하였다. 진동대 실험을 바탕으로 UPS의 손상양상 및 고유진동수, 감쇠비. 동증폭계수, 상대변위 등 동적특성을 비교 및 분석하였다. 3가지 유형의 복합면지장치를 적용함에 따라 UPS의 내진성능이 향상되었으며 이를 통해 개발 면진장치의 성능을 검증하였다.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > School of Architecture > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Choi, Kyoung-Kyu photo

Choi, Kyoung-Kyu
College of Engineering (School of Architecture)
Read more

Altmetrics

Total Views & Downloads

BROWSE