Analysis on Protection Coordination of OCRs Using Index for Impedance Compensation Considering Unsymmetrical Ground Fault in a Power Distribution System With SFCL

Full metadata record
DC Field Value Language
dc.contributor.authorCho, Yoo Jung-
dc.contributor.authorLim, Sung-Hun-
dc.date.accessioned2023-09-04T05:40:05Z-
dc.date.available2023-09-04T05:40:05Z-
dc.date.created2023-09-04-
dc.date.issued2023-08-
dc.identifier.issn1051-8223-
dc.identifier.urihttp://scholarworks.bwise.kr/ssu/handle/2018.sw.ssu/44219-
dc.description.abstractThe superconducting fault current limiter (SFCL) has been spotlighted as the effective device to limit the fault current because it has no effect on a power distribution system in a normal time due to its zero resistance. However, the SFCL causes the trip of the overcurrent relays (OCRs) to be delayed due to the reduction of the fault current, which causes a negative impact on the protection coordination of power distribution system. The delayed trip of OCR makes the exposure time's increase of the neighboring power facilities from the fault current at fault line. In this paper, the OCR's index for the impedance compensation of the SFCL in case of the unsymmetrical ground fault was suggested. The suggested OCR's index consists of all sequence components for the impedance, calculated from the voltages and the currents measured from both the power distribution system and the SFCL. To prove the effectiveness of algorithm, the protection coordination between OCRs in a power distribution system with the SFCL were analyzed for the unsymmetrical ground fault as well as the symmetrical ground fault through the simulation using power system computer aided design (PSCAD)/electromagnetic transient design and control (EMTDC).-
dc.language영어-
dc.language.isoen-
dc.publisherIEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC-
dc.relation.isPartOfIEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY-
dc.titleAnalysis on Protection Coordination of OCRs Using Index for Impedance Compensation Considering Unsymmetrical Ground Fault in a Power Distribution System With SFCL-
dc.typeArticle-
dc.identifier.doi10.1109/TASC.2023.3262765-
dc.type.rimsART-
dc.identifier.bibliographicCitationIEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, v.33, no.5-
dc.description.journalClass1-
dc.identifier.wosid001037733400001-
dc.identifier.scopusid2-s2.0-85151573262-
dc.citation.number5-
dc.citation.titleIEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY-
dc.citation.volume33-
dc.contributor.affiliatedAuthorLim, Sung-Hun-
dc.identifier.urlhttps://ieeexplore.ieee.org/document/10086578-
dc.type.docTypeArticle-
dc.description.isOpenAccessN-
dc.subject.keywordAuthorSuperconducting fault current limiter (SFCL)-
dc.subject.keywordAuthorover current relay (OCR)-
dc.subject.keywordAuthorprotection coordination-
dc.subject.keywordAuthorimpedance compensation-
dc.subject.keywordAuthorunsymmetrical ground fault-
dc.subject.keywordAuthorpower distribution system-
dc.relation.journalResearchAreaEngineering-
dc.relation.journalResearchAreaPhysics-
dc.relation.journalWebOfScienceCategoryEngineering, Electrical & Electronic-
dc.relation.journalWebOfScienceCategoryPhysics, Applied-
dc.description.journalRegisteredClassscie-
dc.description.journalRegisteredClassscopus-
Files in This Item
Go to Link
Appears in
Collections
College of Engineering > School of Electrical Engineering > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Lim, Sung Hun photo

Lim, Sung Hun
College of Engineering (School of Electrical Engineering)
Read more

Altmetrics

Total Views & Downloads

BROWSE