객차내 환기속도가 고압 미세물분무 화재제어 시스템 성능에 미치는 영향에 대한 실험적 연구An Experimental Study for the Effect of Ventilation Velocity on Performance of a High Pressure Water Mist Fire Suppression System
- Authors
- 김동운; 배승용; 유홍선
- Issue Date
- 2008
- Publisher
- 한국안전학회
- Keywords
- water mist; suppression system; ventilation velocity
- Citation
- 한국안전학회지, v.23, no.4, pp 1 - 6
- Pages
- 6
- Journal Title
- 한국안전학회지
- Volume
- 23
- Number
- 4
- Start Page
- 1
- End Page
- 6
- URI
- https://scholarworks.bwise.kr/cau/handle/2019.sw.cau/31301
- ISSN
- 1738-3803
- Abstract
- This experiments are performed to investigate the effect of ventilation velocity on a high pressure water mist fire suppression in train. The experiment is conducted in half scale modeled train of a steel-welled enclosure (5.0m×2.4m×2.2m). The ventilation velocity is controlled by the ventilation duct through an inverter in the range of 0 to 3m/s. The coverage-radius and an injection angle of an high pressure water mist system are measured. The mist nozzle with 5-injection holes is operated with pressure 60bar. The heptane pool fires are used. The fire extinguishment times and the temperature are measured for the ventilation velocities. In conclusion, because the momentum of injected water mist is more dominant than that of ventilation air, the characteristics of water mist, the fire extinguishment times and the temperature are affected very little by ventilation velocity.
- Files in This Item
- There are no files associated with this item.
- Appears in
Collections - College of Engineering > School of Mechanical Engineering > 1. Journal Articles
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.