Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

객차내 환기속도가 고압 미세물분무 화재제어 시스템 성능에 미치는 영향에 대한 실험적 연구An Experimental Study for the Effect of Ventilation Velocity on Performance of a High Pressure Water Mist Fire Suppression System

Authors
김동운배승용유홍선
Issue Date
2008
Publisher
한국안전학회
Keywords
water mist; suppression system; ventilation velocity
Citation
한국안전학회지, v.23, no.4, pp 1 - 6
Pages
6
Journal Title
한국안전학회지
Volume
23
Number
4
Start Page
1
End Page
6
URI
https://scholarworks.bwise.kr/cau/handle/2019.sw.cau/31301
ISSN
1738-3803
Abstract
This experiments are performed to investigate the effect of ventilation velocity on a high pressure water mist fire suppression in train. The experiment is conducted in half scale modeled train of a steel-welled enclosure (5.0m×2.4m×2.2m). The ventilation velocity is controlled by the ventilation duct through an inverter in the range of 0 to 3m/s. The coverage-radius and an injection angle of an high pressure water mist system are measured. The mist nozzle with 5-injection holes is operated with pressure 60bar. The heptane pool fires are used. The fire extinguishment times and the temperature are measured for the ventilation velocities. In conclusion, because the momentum of injected water mist is more dominant than that of ventilation air, the characteristics of water mist, the fire extinguishment times and the temperature are affected very little by ventilation velocity.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > School of Mechanical Engineering > 1. Journal Articles

qrcode