원내 공기감염 확산 방지를 위한 격리병실의 CFD 해석CFD Simulation of the AII-Room for Preventing Spread of the Air-Borne Infection in Hospital

Authors
Yang, Young KwonKang, In SungWon, An-NaHwang, Jung HaPark, Jin Chul
Issue Date
Mar-2017
Publisher
대한건축학회
Keywords
의료시설; 격리병실; 기밀성능; 공기감염; 전산유체역학; Hospital; AII(Air-borne Infection Isolation)Room; Air Leakage; ]Air-borne infection; CFD(Computational Fluid Dynamics)
Citation
대한건축학회논문집 구조계, v.33, no.3, pp 61 - 68
Pages
8
Journal Title
대한건축학회논문집 구조계
Volume
33
Number
3
Start Page
61
End Page
68
URI
https://scholarworks.bwise.kr/cau/handle/2019.sw.cau/5869
DOI
10.5659/JAIK_SC.2017.33.3.61
ISSN
1226-9107
Abstract
The present study is a foundational study for performance improvements on isolation wards to prevent proliferation of secondary infection of infectious diseases such as SARS, H1N1, and MERS inside hospitals. Accordingly, the present study conducted an analysis of the effect of sealing mechanisms and filling of openings on ensuring air tightness performance in isolation wards as well as simulation on air currents in improved isolation wards. The study method is as follows: first, previous studies on aerial infection types and mechanisms were reviewed and the review results were utilized as basic data for analysis of the simulation of air currents. Second, national and international legislations and regulations in relation to isolation wards as well as case studies on developed nations were investigated in order to identify the problems in isolation wards in Korea and improvement plans. Third, construction and facility plans were compared and analyzed between general and isolation wards focusing on large general hospitals in Korea thereby conducting comparison and analysis on the performance and effects of air-tightness of general and isolation wards through simulations(CFD). Fourth, an analysis on air currents in isolation wards specified in mandatory legislation (draft) from the Ministry of Health and Welfare such as fulfillment of isolation ward requirements including negative pressure isolation wards, areas of ward and intensive care units, and ensuring separation distance between sickbeds was conducted. The study result showed that isolation wards had better air-tightness performance than that of general wards and parallel bed layout was better than serial bed layout in terms of aerial infection substance proliferation. In addition, when a separation distance between sickbeds was 2m or wider, the risk of aerial infection became significantly lower.
The present study is a foundational study for performance improvements on isolation wards to prevent proliferation of secondary infection of infectious diseases such as SARS, H1N1, and MERS inside hospitals. Accordingly, the present study conducted an analysis of the effect of sealing mechanisms and filling of openings on ensuring air tightness performance in isolation wards as well as simulation on air currents in improved isolation wards. The study method is as follows: first, previous studies on aerial infection types and mechanisms were reviewed and the review results were utilized as basic data for analysis of the simulation of air currents. Second, national and international legislations and regulations in relation to isolation wards as well as case studies on developed nations were investigated in order to identify the problems in isolation wards in Korea and improvement plans. Third, construction and facility plans were compared and analyzed between general and isolation wards focusing on large general hospitals in Korea thereby conducting comparison and analysis on the performance and effects of air-tightness of general and isolation wards through simulations(CFD). Fourth, an analysis on air currents in isolation wards specified in mandatory legislation (draft) from the Ministry of Health and Welfare such as fulfillment of isolation ward requirements including negative pressure isolation wards, areas of ward and intensive care units, and ensuring separation distance between sickbeds was conducted. The study result showed that isolation wards had better air-tightness performance than that of general wards and parallel bed layout was better than serial bed layout in terms of aerial infection substance proliferation. In addition, when a separation distance between sickbeds was 2m or wider, the risk of aerial infection became significantly lower.
Files in This Item
There are no files associated with this item.
Appears in
Collections
College of Engineering > ETC > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Park, Jin Chul photo

Park, Jin Chul
공과대학 (건축공학)
Read more

Altmetrics

Total Views & Downloads

BROWSE