Consideration of the Insulation Design Method on a ± 200 kV Converter Valve Unit in an HVDC Converter Hall
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Bang, Seungmin | - |
dc.contributor.author | Kim, Ho-Seung | - |
dc.contributor.author | Koo, Jae-Hong | - |
dc.contributor.author | Lee, Bang-Wook | - |
dc.date.accessioned | 2023-08-16T07:35:12Z | - |
dc.date.available | 2023-08-16T07:35:12Z | - |
dc.date.issued | 2021-04 | - |
dc.identifier.issn | 1996-1073 | - |
dc.identifier.issn | 1996-1073 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/erica/handle/2021.sw.erica/113903 | - |
dc.description.abstract | A converter valve unit, which converts Alternating Current (AC) to Directing Current (DC) and DC to AC, is one of the key elements of high voltage direct current (HVDC) transmission. The insulation design of a converter valve unit should be considered for air clearance according to the DC superimposed overvoltage and the insulator that maintains the insulation performance and the corona shield to suppress DC corona discharge. There is no prescribed standard for the insulation design of a converter valve unit. Moreover, insulation performance under an applied DC voltage has not yet been thoroughly investigated. Therefore, it is necessary to study the insulation design method of the converter valve unit. In this paper, consideration of the insulation design method on a ±200 kV converter valve unit in an HVDC converter hall is performed. The finite element method (FEM) is used to simulate the 3D model. Additionally, the safety factor (SF) is applied in accordance with the dielectric test in IEC 62271-1. As a result, an insulation design process on the converter valve unit is proposed and the insulation design is carried through the design factors. It is confirmed that design factors on the air clearance, insulator and corona shield have a significant effect on a highly reliable insulation design. © 2021 by the authors. Licensee MDPI, Basel, Switzerland. | - |
dc.format.extent | 18 | - |
dc.language | 영어 | - |
dc.language.iso | ENG | - |
dc.publisher | Multidisciplinary Digital Publishing Institute (MDPI) | - |
dc.title | Consideration of the Insulation Design Method on a ± 200 kV Converter Valve Unit in an HVDC Converter Hall | - |
dc.type | Article | - |
dc.publisher.location | 스위스 | - |
dc.identifier.doi | 10.3390/en14082296 | - |
dc.identifier.scopusid | 2-s2.0-85106292625 | - |
dc.identifier.wosid | 000644115900001 | - |
dc.identifier.bibliographicCitation | Energies, v.14, no.8, pp 1 - 18 | - |
dc.citation.title | Energies | - |
dc.citation.volume | 14 | - |
dc.citation.number | 8 | - |
dc.citation.startPage | 1 | - |
dc.citation.endPage | 18 | - |
dc.type.docType | 정기학술지(Article(Perspective Article포함)) | - |
dc.description.isOpenAccess | Y | - |
dc.description.journalRegisteredClass | scie | - |
dc.description.journalRegisteredClass | scopus | - |
dc.relation.journalResearchArea | Energy & Fuels | - |
dc.relation.journalWebOfScienceCategory | Energy & Fuels | - |
dc.subject.keywordAuthor | Air clearance | - |
dc.subject.keywordAuthor | Converter valve | - |
dc.subject.keywordAuthor | Corona shield | - |
dc.subject.keywordAuthor | DC corona inception electric field | - |
dc.subject.keywordAuthor | FEM | - |
dc.subject.keywordAuthor | Flashover | - |
dc.subject.keywordAuthor | HVDC | - |
dc.subject.keywordAuthor | Insulator | - |
dc.subject.keywordAuthor | Overvoltage | - |
dc.subject.keywordAuthor | Triple point | - |
dc.identifier.url | https://www.scopus.com/record/display.uri?eid=2-s2.0-85106292625&origin=inward&txGid=a5617bae03828f3180a23a54f8cc90b7 | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
55 Hanyangdeahak-ro, Sangnok-gu, Ansan, Gyeonggi-do, 15588, Korea+82-31-400-4269 sweetbrain@hanyang.ac.kr
COPYRIGHT © 2021 HANYANG UNIVERSITY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.