Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Analysis of Deterioration Characteristics of Service-Aged XLPE Cables According to Installation Location of Combined Heat and Power Plant

Full metadata record
DC Field Value Language
dc.contributor.authorKim, Ho-Seung-
dc.contributor.authorJung, Jiho-
dc.contributor.authorLee, Bang-Wook-
dc.date.accessioned2024-05-21T08:30:23Z-
dc.date.available2024-05-21T08:30:23Z-
dc.date.issued2024-05-
dc.identifier.issn1996-1073-
dc.identifier.issn1996-1073-
dc.identifier.urihttps://scholarworks.bwise.kr/erica/handle/2021.sw.erica/119065-
dc.description.abstractThe number of XLPE cables being used near or beyond their design life is increasing. The importance of timely cable replacement is necessary. Therefore, research is actively being conducted using VLF Tan δ diagnostic technology to assess the insulation condition of cables. Present studies lack in measuring and analyzing the VLF Tan δ of service-aged XLPE cables. Additionally, there is a research gap considering the operating environment. Therefore, it is needed to diagnose and analyze the insulation condition of the same service-aged cable when it is operated in a different environment. This paper assesses and analyzes the insulation condition of cables installed in the BFP, cooling tower, and deaerator booster pump of a combined heat and power plant. Each cable was evaluated by measuring the VLF Tan δ, the dielectric breakdown test of the cable, and the tensile strength, elongation at break, crystallinity, and dielectric strength of the XLPE specimens. Additionally, the correlation between the VLF Tan δ and other characteristics was also analyzed. It was found that degradation progressed in the order of the BFP, the cooling tower, and the deaerator booster pump. Therefore, it was confirmed that even for the same cable, deterioration varies depending on the installation location. © 2024 by the authors.-
dc.format.extent15-
dc.language영어-
dc.language.isoENG-
dc.publisherMultidisciplinary Digital Publishing Institute (MDPI)-
dc.titleAnalysis of Deterioration Characteristics of Service-Aged XLPE Cables According to Installation Location of Combined Heat and Power Plant-
dc.typeArticle-
dc.publisher.location스위스-
dc.identifier.doi10.3390/en17092024-
dc.identifier.scopusid2-s2.0-85192777954-
dc.identifier.wosid001219955200001-
dc.identifier.bibliographicCitationEnergies, v.17, no.9, pp 1 - 15-
dc.citation.titleEnergies-
dc.citation.volume17-
dc.citation.number9-
dc.citation.startPage1-
dc.citation.endPage15-
dc.type.docTypeArticle-
dc.description.isOpenAccessY-
dc.description.journalRegisteredClassscie-
dc.description.journalRegisteredClassscopus-
dc.relation.journalResearchAreaEnergy & Fuels-
dc.relation.journalWebOfScienceCategoryEnergy & Fuels-
dc.subject.keywordAuthorBFP-
dc.subject.keywordAuthorcooling tower-
dc.subject.keywordAuthorcorrelation with Tan δ-
dc.subject.keywordAuthordeaerator booster pump-
dc.subject.keywordAuthorservice-aged XLPE cable-
dc.identifier.urlhttps://www.mdpi.com/1996-1073/17/9/2024-
Files in This Item
Go to Link
Appears in
Collections
COLLEGE OF ENGINEERING SCIENCES > SCHOOL OF ELECTRICAL ENGINEERING > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Lee, Bang Wook photo

Lee, Bang Wook
ERICA 공학대학 (SCHOOL OF ELECTRICAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE