Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

Black-box 아크 모델의 비선형 특성을 활용한 고체 절연물 내 보이드에 의한 부분방전 해석모델 개발Development of Partial Discharge Analysis Model by Void in Solid Insulation Using Nonlinear Characteristics of Black-box Arc Model

Other Titles
Development of Partial Discharge Analysis Model by Void in Solid Insulation Using Nonlinear Characteristics of Black-box Arc Model
Authors
주형준이종건한기선박규훈이방욱
Issue Date
Nov-2020
Publisher
대한전기학회
Keywords
Partial Discharge Simulation; Void; Capacitive Equivalent model; Black-Box Arc Model; Nonlinear Characteristics
Citation
전기학회논문지, v.69, no.11, pp 1707 - 1716
Pages
10
Indexed
SCOPUS
KCI
Journal Title
전기학회논문지
Volume
69
Number
11
Start Page
1707
End Page
1716
URI
https://scholarworks.bwise.kr/erica/handle/2021.sw.erica/1528
DOI
10.5370/KIEE.2020.69.11.1707
ISSN
1975-8359
2287-4364
Abstract
Partial discharge measurement and analysis of solid insulators should be performed indispensably for predicting the insulation life and diagnosis of electric power facilities. Prior to the actual partial discharge measurement, the partial discharge can be analyzed through a simulation study based on the design of an accurate equivalent model of the insulating materials. The high reliability of partial discharge simulation can reduce cost, manpower, and time required when performing actual partial discharge measurement tests, and can be effectively applied to complex partial discharge characteristics analysis of insulating materials. In this paper, a partial discharge simulation was performed by designing an equivalent model of a partial discharge test cell injected with a small circular void in the inner center. To evaluate the reliability of the simulation results, the actual partial discharge of the test cell was measured according to the test procedure of IEC-60270. A capacitive equivalent model that can simulate the partial discharge characteristics of the test cell was designed and a simulation study of partial discharge inside the insulator was conducted. The partial discharge measurement system is designed using a black-box arc model that can describe the nonlinear characteristics of the arc. The parameters of the simulation model were selected by establishing a simulation scenario assuming the condition of adding electrical deterioration to the voids of the same size. In addition, to verify the simulation results, PRPD (Phase Resolved Partial Discharge) patterns generated in voids was obtained using a partial discharge measuring device. The parameters related to the partial discharge characteristics such as the maximum partial discharge amplitude, number and distribution were investigated. As a result, the consistency of the partial discharge simulation results was verified through a comparative study of simulation and test results, and a reliable partial discharge modeling technique was established.
Files in This Item
Go to Link
Appears in
Collections
COLLEGE OF ENGINEERING SCIENCES > SCHOOL OF ELECTRICAL ENGINEERING > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Lee, Bang Wook photo

Lee, Bang Wook
ERICA 공학대학 (SCHOOL OF ELECTRICAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE