Validity Analysis on the Positioning of Superconducting Fault Current Limiter in Neighboring AC and DC Microgrid
DC Field | Value | Language |
---|---|---|
dc.contributor.author | Hwang, Jae-Sang | - |
dc.contributor.author | Khan, Umer. A. | - |
dc.contributor.author | Shin, Woo-Ju | - |
dc.contributor.author | Seong, Jae-Kyu | - |
dc.contributor.author | Lee, Jong-Geon | - |
dc.contributor.author | Kim, Yong-Han | - |
dc.contributor.author | Lee, Bang-Wook | - |
dc.date.accessioned | 2021-06-23T03:22:12Z | - |
dc.date.available | 2021-06-23T03:22:12Z | - |
dc.date.issued | 2013-06 | - |
dc.identifier.issn | 1051-8223 | - |
dc.identifier.issn | 1558-2515 | - |
dc.identifier.uri | https://scholarworks.bwise.kr/erica/handle/2021.sw.erica/27951 | - |
dc.description.abstract | In a smart grid, various kinds of distributed generation (DG) sources could be connected into the main power grid in order to enhance the reliability of the power system. The combination of ac and dc distribution grid are also considered for the efficient connection of renewable power resources. In this case, one of the critical problems due to these integrations is the excessive increase in the fault current because of the presence of DG within the smart grid. In order to protect the smart grid from increasing fault current, a superconducting fault current limiter (SFCL) could be applied, which has negligible power loss and capability to limit initial fault currents effectively. This paper presents feasibility analysis results of the positioning of the SFCL and its effects on reducing fault current in a smart grid having ac and dc microgrid. The detailed power system was implemented with a microgrid having wind farm and low voltage dc grid connected with a photovoltaic farm. Transient analyses were performed for the worst case faults with the different SFCL arrangements. The strategic location of SFCL in the power grid, which could limit fault currents and has no negative effect on the DG sources, was found to be the connection point of integration of the each DG sources in the ac and dc microgrid. | - |
dc.language | 영어 | - |
dc.language.iso | ENG | - |
dc.publisher | Institute of Electrical and Electronics Engineers | - |
dc.title | Validity Analysis on the Positioning of Superconducting Fault Current Limiter in Neighboring AC and DC Microgrid | - |
dc.type | Article | - |
dc.publisher.location | 미국 | - |
dc.identifier.doi | 10.1109/TASC.2012.2228735 | - |
dc.identifier.scopusid | 2-s2.0-84872125251 | - |
dc.identifier.wosid | 000314275800097 | - |
dc.identifier.bibliographicCitation | IEEE Transactions on Applied Superconductivity, v.23, no.3 | - |
dc.citation.title | IEEE Transactions on Applied Superconductivity | - |
dc.citation.volume | 23 | - |
dc.citation.number | 3 | - |
dc.type.docType | Article | - |
dc.description.isOpenAccess | N | - |
dc.description.journalRegisteredClass | sci | - |
dc.description.journalRegisteredClass | scie | - |
dc.description.journalRegisteredClass | scopus | - |
dc.relation.journalResearchArea | Engineering | - |
dc.relation.journalResearchArea | Physics | - |
dc.relation.journalWebOfScienceCategory | Engineering, Electrical & Electronic | - |
dc.relation.journalWebOfScienceCategory | Physics, Applied | - |
dc.subject.keywordAuthor | Distributed generation (DG) sources | - |
dc.subject.keywordAuthor | fault current | - |
dc.subject.keywordAuthor | microgrid | - |
dc.subject.keywordAuthor | neighboring grid | - |
dc.subject.keywordAuthor | protection devices | - |
dc.subject.keywordAuthor | smart grid | - |
dc.subject.keywordAuthor | superconducting fault current limiter | - |
dc.identifier.url | https://ieeexplore.ieee.org/document/6355629/ | - |
Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.
55 Hanyangdeahak-ro, Sangnok-gu, Ansan, Gyeonggi-do, 15588, Korea+82-31-400-4269 sweetbrain@hanyang.ac.kr
COPYRIGHT © 2021 HANYANG UNIVERSITY. ALL RIGHTS RESERVED.
Certain data included herein are derived from the © Web of Science of Clarivate Analytics. All rights reserved.
You may not copy or re-distribute this material in whole or in part without the prior written consent of Clarivate Analytics.