dc.description.abstractSuperconducting fault current limiter (SFCL) is a promising novel electric equipment to reduce excessive fault current in electric power systems effectively. However, in practical application of this novel device into electric networks, SFCL could cause some unfavorable impacts on the electric power system. Especially, coordination between the SFCL and the recloser which has a conventional protection scheme is a major concern because it could cause severe reliability and stability problems in power systems. Several important characteristics of SFCL, which affects on a recloser operation scheme, are quenching phenomena, recovery from the quenching state, limiting impedance and its triggering time. Therefore, careful assessment of coordination issues with a recloser should be investigated to evaluate reliabilities of electric power system by installing SFCL into conventional power networks. This paper presents the impacts of SFCL on the recloser operation by considering various aspects of newly developed hybrid resistive SFCL into distribution systems in Korea. Consequently, it was deduced that conventional recloser scheme might be altered in order to meet the performance and requirements of hybrid SFCL into distribution electric power systems.-
dc.format.extent4-
dc.language영어-
dc.language.isoENG-
dc.publisherInstitute of Electrical and Electronics Engineers-
dc.titleImpacts of Superconducting Fault Current Limiters on the Recloser Operation in Distribution Electric Power Systems-
dc.typeArticle-
dc.publisher.location미국-
dc.identifier.doi10.1109/TASC.2010.2089958-
dc.identifier.scopusid2-s2.0-79957907122-
dc.identifier.wosid000291054200295-
dc.identifier.bibliographicCitationIEEE Transactions on Applied Superconductivity, v.21, no.3, pp 2197 - 2200-
dc.citation.titleIEEE Transactions on Applied Superconductivity-
dc.citation.volume21-
dc.citation.number3-
dc.citation.startPage2197-
dc.citation.endPage2200-
dc.type.docTypeArticle-
dc.description.isOpenAccessN-
dc.description.journalRegisteredClasssci-
dc.description.journalRegisteredClassscie-
dc.description.journalRegisteredClassscopus-
dc.relation.journalResearchAreaEngineering-
dc.relation.journalResearchAreaPhysics-
dc.relation.journalWebOfScienceCategoryEngineering, Electrical & Electronic-
dc.relation.journalWebOfScienceCategoryPhysics, Applied-
dc.subject.keywordAuthorEMTP-
dc.subject.keywordAuthorfault current-
dc.subject.keywordAuthorpower systems-
dc.subject.keywordAuthorrecloser-
dc.subject.keywordAuthorsuperconducting fault current limiter-
dc.identifier.urlhttps://ieeexplore.ieee.org/document/5654553-
Files in This Item
Go to Link
Appears in
Collections
COLLEGE OF ENGINEERING SCIENCES > SCHOOL OF ELECTRICAL ENGINEERING > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Lee, Bang Wook photo

Lee, Bang Wook
ERICA 공학대학 (SCHOOL OF ELECTRICAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE