Heat pump를 적용한 액체식 제습 시스템의 겨울철 가습 운전에 대한 실험적 연구Experimental study for humidification operation of heat pump integrated liquid desiccant system in winter
- Other Titles
- Experimental study for humidification operation of heat pump integrated liquid desiccant system in winter
- Authors
- 임한솔; 이수진; 동혜원; 조혜진; 정재원
- Issue Date
- Nov-2019
- Publisher
- (사)대한설비공학회
- Keywords
- Liquid desiccant system; Regenerator; Humidification; Lithium chloride; 액체식 제습 시스템; 재생기; 가습; 염화 리튬
- Citation
- 대한설비공학회 2019 동계학술발표대회 논문집, pp.261 - 264
- Indexed
- OTHER
- Journal Title
- 대한설비공학회 2019 동계학술발표대회 논문집
- Start Page
- 261
- End Page
- 264
- URI
- https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/146760
- Abstract
- The performance of regenerator in heat pump integrated liquid desiccant (LD) system was investigated for the operation in winter. The performance parameters for regenerator were the regeneration effectiveness and enthalpy exchange effectiveness. There were five independent parameters of inlet air temperature, inlet air humidity ratio, inlet solution temperature, concentration of solution and liquid-to-gas ratio. The experimental model was constructed using an adiabatic cross flow regenerator with lithium chloride solution. Based on 2k and 3k factorial design method, total 48 experiment sets were designed to develop prediction models for two performance parameters. The results showed that the solution temperature and liquit-to-gas ratio have significant effects on the regeneration effectiveness and enthalpy exchange effectiveness of regenerator. In addition, the amount of humidification was ranged from 3.23 g/㎏a to 51.18 g/㎏a, therefore it was enough for humidification system in winter.
- Files in This Item
-
Go to Link
- Appears in
Collections - 서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.