Detailed Information

Cited 0 time in webofscience Cited 0 time in scopus
Metadata Downloads

간접식 증발냉각 시스템의 공기유동 방법에 따른 성능 분석Experimental comparison of the performance of typical and regenerative indirect evaporative coolers

Other Titles
Experimental comparison of the performance of typical and regenerative indirect evaporative coolers
Authors
윤동섭김희정김원준정재원
Issue Date
Nov-2016
Publisher
한국건축친환경설비학회
Keywords
간접식 증발냉각 시스템; 재생형 증발냉각; 열교환기; Indirect evaporative cooler; Regenerative evaporative cooler; Heat exchanger
Citation
한국건축친환경설비학회 추계학술발표대회, 2016 (2016-11), pp.49 - 50
Indexed
OTHER
Journal Title
한국건축친환경설비학회 추계학술발표대회, 2016 (2016-11)
Start Page
49
End Page
50
URI
https://scholarworks.bwise.kr/hanyang/handle/2021.sw.hanyang/153507
Abstract
The main purpose of this research is to compare the performances of two selected operation modes in an indirect evaporative cooler: typical cross-flow operation and regenerative operation using outdoor air as redirected air. To compare the performance of each operation mode, experiments were conducted with changing outdoor air condition and airflow rate. Pressure drop and leaving air temperature were measured to evaluate the performances quantitatively. As the experimental results, better performance indices were shown with the typical cross-flow operation than regenerative operation showing higher wet bulb effectiveness, lower pressure drop, and lower leaving air temperature.
Files in This Item
Go to Link
Appears in
Collections
서울 공과대학 > 서울 건축공학부 > 1. Journal Articles

qrcode

Items in ScholarWorks are protected by copyright, with all rights reserved, unless otherwise indicated.

Related Researcher

Researcher Jeong, Jae Weon photo

Jeong, Jae Weon
COLLEGE OF ENGINEERING (SCHOOL OF ARCHITECTURAL ENGINEERING)
Read more

Altmetrics

Total Views & Downloads

BROWSE